33
OPERATION
GFCI System
②
(120V-20A Duplex Receptacle)
1. Unplug all tools and appliances from the generator.
2. Start the engine (see page 26).
3. Turn the AC circuit breaker to the ON position.
4. Turn OFF the auto throttle switch (see page 27).
5. Press the TEST button:
• The RESET button should extend.
• If the GFCI does not function as described, contact an authorized
Honda generator dealer.
GFCI TEST BUTTON
AUTO THROTTLE SWITCH
AC CIRCUIT BREAKER
GFCI SYSTEM
②
(120V-20A DUPLEX RECEPTACLES)
GFCI RESET BUTTON
ON