10.2.1 Meter Control Message (MCMHDR) defined as:
Bit#
7
6
5
4
Part
Version,
Highbit
Version, LowBit
Send Readings
Send Now
Bit#
3
2
1
0
Part
RFU
RFU
RFU
RFU
Execution
Version Bits
description
00
LoRaWAN Meter Protocol V1
01..11
RFU
Send Readings
Send Readings Bit
description
0
Off, do not send any uplink packets at the defined intervals until
the bit is set to 1 again. No messages (neither confirmed nor
unconfirmed) will be sent. The meter just keeps listening to new
commands.
1
On, send readings at the defined intervals
Send Now (To a single read, regardless of the sending interval)
Send Now bit
description
0
Off, no need to send an additional meter reading in response to this
message.
1
On, regardless of the other parameters, the electricity meter as soon as
the duty cycle allows reading. Even if the “Send Reading Bit” is 0.
10.2.2 Unconfirmed Interval
4 byte integer denotes the multiple of 1 minute long interval in which the meter readings are sent as an unconfirmed