When one of the following conditions is met, defrosting operation will be switched to
heating operation.
(
1
)
:Temperature of outdoor heat exchanger exceeds 7 for 80s continuously
℃
(
2
)
:Temperature of outdoor heat exchanger exceeds 12 for 5s continuously
℃
(
3
)
:Defrosting operation continues for 9 minutes.
E. When defrosting exit conditions are met, the unit will operate as follows
Compressor stops and external fan starts, 50s later, four-way valve will be on, 60s
later, compressor will operate as per startup process.
1.6:PTC Output Control
z
When outdoor unit is energized, PTC output value is 0, 10s later, output value is 1.
z
When compressor stops for 10 minutes continuously, PTC output value is 0.
z
On receiving compressor startup instruction, initial PTC output is 1, and compressor
startup will be performed 5s later.
Two. System Protection Function
2.1:Time interval between compressor shutdown and restart is set at 3 minutes to ensure that
compressor will only restart after 3-minute shutdown and initial energization valves are turned on
to adequate opening position after being fully turned off.
2.2:TD High Temperature Protection
As long as unit is on, the TD air discharge overheat protection feature will be activated, yet
air discharge sensor fault must be alarmed 4 minutes after compressor starts.
TD
(
℃
)
Abnormal Shutdown
117
rapid frequency drop
(
1HZ/s
)
1
09
slow frequency drop (1HZ/10s)
9
8
invariable frequency
93
frequency rise (1HZ/10s)
9
0
frequency rise
(
1HZ/1s
)
When TD
>
117 for 20s continuously
℃
,
air discharge overheat protection will be activated and
fault will be reported to indoor unit.
In other protection features, there is no continuous allowance.
2.3: Indoor unit TC high temperature prevention and control in heating mode:
Indoor heat exchanger sensor will check temperature of indoor heat exchanger, if the
temperature is higher than 55 ,
℃
compressor rotate speed will be reduced to activate indoor heat
exchanger high temperature protection. When temperature of indoor heat exchanger falls below
48 , normal control will be resumed.
℃
TC
65
P Slow Drop
55
Q Maintain
52
48
R Slow Rise
P: Drop at the speed of 1Hz/10s
Classic Line Air Conditioner
Model: HKEN-HCNN 642 XR
Содержание HKEN-HCNN 642XR
Страница 2: ...CONTENT Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 3: ...SERIES INTRODUCTION Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 5: ...SPECIFICATIONS Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 7: ...CURVES OF PERFORMANCE OF COMPRESSOR Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 12: ...KNOCK DOWN DRAWINGS Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 13: ...Model HSU 18H03 R2 DB Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 15: ...BRIEF INTRODUCTION TO ELECTRICAL CONTROL FUNCTIONS Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 27: ...WIRING DIAGRAM Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 28: ...Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 30: ...CIRCUIT DIAGRAM Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 33: ...ABNORMITY DIAGNOSE Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 36: ...TROUBLE SHOOTING Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 37: ...Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 38: ...REFRIGERATING CYCLE DIAGRAM Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 39: ...Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 40: ...NOISE LEVEL TEST CHART AND AIR VELOCITY DISTRIBUTION Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 43: ...INSTALLATION MANUAL Classic Line Air Conditioner Model HKEN HCNN 642 XR ...