One. System Major Function
Sensor Code Definition: Tai= Indoor Ambient Temperature, Tao=Outdoor Ambient
Temperature, Tc1=Indoor Coil, Td= Air Discharge, Te= Outdoor Coil, Ts=Air Intake
1.1: Outdoor Unit Operation Frequency and Control
1.1.1: Compressor Operation Frequency Control
z
Compressor Operation Frequency Range:
Outdoor Temperature
~0
℃
0
℃
~
Heating
17RPM 110RPM 17RPM 120RPM
Cooling
20RPM 110RPM 20RPM 120RPM
Defrosting
88rpm
1.1.2: Compressor Startup
Regardless of target frequency of indoor unit, each time when compressor is from off to on, it
must maintain 60Hz and 90Hz for one minute respectively (Frequency will be immediately
decreased under the condition that outdoor unit air discharge temperature overheating protection
is activated or overcurrent of compressor) then the compressor will operate towards target
frequency. This process does not exist in normal operation of unit.
1.1.3:Heating:
z
When completing compressor startup operation, it will operate as per frequency of
indoor unit.
z
After 2 minutes, compressor operation frequency will be compensated as per relevant
conditions.
1.1.4 Cooling & Dehumidification:
z
When completing compressor startup operation, it will operate as per frequency of
indoor unit.
z
After 2 minutes, compressor operation frequency will be compensated as per relevant
conditions.
1.1.5: Compressor Frequency Increase/Decrease Speed
Rapid Frequency Increase/Decrease Speed 1 ----------1HZ/s
Slow Frequency Increase/Decrease Speed 2 -----------1HZ/10s
1.2: Outdoor Fan Control
1.2.1: Wind speed control when AC fan is adopted for outdoor unit.
z
Whether to use AC fan or DC fan is determined by EEPROM
z
Residual Heat Blow: After compressor shuts down in cooling mode, fan will run for 30s at low
speed before stop.
z
Wind Speed Adjustment Table (when compressor starts up for 3 minutes)
Ambient
Temperature ~10 10~25 25~
Cooling & Dehumidification
Low Wind
Low Wind
High Wind
Heating
High Wind
Low Wind
Low Wind
z
Wind
Speed
Adjustment
Table
(based on ambient temperature and compressor frequency after compressor runs for 3
minutes)
Cooling Compressor Frequency
F<25Hz
25Hz<=F<45Hz
45Hz<=F
Above 28
℃
Low Wind
High Wind
High Wind
Tao
Below 28
℃
Low Wind
Low Wind
High Wind
Heating Compressor Frequency
F<25Hz
25Hz
≤
F<45Hz 45Hz
≤
f
Classic Line Air Conditioner
Model: HKEN-HCNN 642 XR
Содержание HKEN-HCNN 642XR
Страница 2: ...CONTENT Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 3: ...SERIES INTRODUCTION Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 5: ...SPECIFICATIONS Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 7: ...CURVES OF PERFORMANCE OF COMPRESSOR Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 12: ...KNOCK DOWN DRAWINGS Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 13: ...Model HSU 18H03 R2 DB Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 15: ...BRIEF INTRODUCTION TO ELECTRICAL CONTROL FUNCTIONS Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 27: ...WIRING DIAGRAM Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 28: ...Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 30: ...CIRCUIT DIAGRAM Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 33: ...ABNORMITY DIAGNOSE Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 36: ...TROUBLE SHOOTING Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 37: ...Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 38: ...REFRIGERATING CYCLE DIAGRAM Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 39: ...Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 40: ...NOISE LEVEL TEST CHART AND AIR VELOCITY DISTRIBUTION Classic Line Air Conditioner Model HKEN HCNN 642 XR ...
Страница 43: ...INSTALLATION MANUAL Classic Line Air Conditioner Model HKEN HCNN 642 XR ...