User Reference Manual - VI96 Display
1.24. Precautions on installation
This instrument has been designed and verified conforming to
the 61010-1 CE Security Regulation, for industrial applications.
Installation of this instrument must be performed by qualified
personnel only. This manual contains the appropriate informa-
tion for the installation. Using the instrument in ways not spe-
cified by the manufacturer may lead to a reduction of the spe-
cified protection level. Disconnect the instrument from power
before starting any maintenance and / or installation action.
The instrument does not have a general switch and will start
operation as soon as power is connected. The instrument does
not have protection fuse, the fuse must be added during ins-
tallation.
The instrument is designed to be panel mounted. An appro-
priate ventilation of the instrument must be assured. Do not
expose the instrument to excess of humidity. Maintain clean
by using a humid rag and do NOT use abrasive products such as
alcohols, solvents, etc.
General recommendations for electrical installations apply, and
for proper functionality we recommend : if possible, install the
instrument far from electrical noise or magnetic field genera-
tors such as power relays, electrical motors, speed variators, ...
If possible, do not install along the same conduits power cables
(power, motor controllers, electrovalves, ...) together with sig-
nal and/or control cables.
Before proceeding to the power connection, verify that the vol-
tage level available matches the power levels indicated in the
label on the instrument.
In case of fire, disconnect the instrument from the power line,
fire alarm according to local rules, disconnect the air conditio-
ning, attack fire with carbonic snow, never with water.
1.25. Warranty
This instrument is warranted against all manufacturing de-
fects for a period of 24 MONTHS from the shipment date. This
warranty does not apply in case of misuse, accident or manipu-
lation by non-authorized personnel. In case of malfunction get
in contact with your local provider to arrange for repair. Within
the warranty period and after examination by the manufactu-
rer, the unit will be repaired or substituted when found to be
defective. The scope of this warranty is limited to the repair
cost of the instrument, not being the manufacturer eligible for
responsibility on additional damages or costs.
1.26. CE declaration of conformity
The manufacturer declares that the instruments indicated
comply with the directives and rules indicated below.
Electromagnetic compatibility directive 2014/30/EU
Low voltage directive 2014/35/EU
Directive ROHS 2011/65/EU
Security rules EN-61010-1
Instrument
Fixed
Permanently connected
Pollution degree 1 and 2 (without condensation)
Isolation
Double
Electromagnetic compatibility rules EN-61326-1
EM environment
Industrial
Immunity levels
EN-61000-4-2 By contact ±4 KV
Criteria B
By air ±8 KV
Criteria B
EN-61000-4-3
Criteria A
EN-61000-4-4 On AC power lines : ±2 KV
Criteria B
On DC power lines : ±2 KV
Criteria B
On signal lines : ±1 KV
Criteria B
EN-61000-4-5 Between AC power lines ±1 KV
Criteria B
Between AC power lines and earth ±2 KV
Criteria B
Between DC power lines ±1 KV
Criteria B
Between DC power lines and earth ±2 KV
Criteria B
Between signal lines and earth ±1 KV
Criteria B
EN-61000-4-6
Criteria A
EN-61000-4-8 30 A/m at 50/60 Hz
Criteria A
EN-61000-4-11 0 % 1 cycle
Criteria A
40 % 10 cycles
Criteria A
70 % 25 cycles
Criteria B
0 % 250 cycles
Criteria B
Emission levels
CISPR 11
Instrument Class A, Group 1
Criteria A
Risk of electrical shock. Instrument terminals can be
connected to dangerous voltage.
Instrument protected with double isolation. No earth
connection required.
Instrument conforms to CE rules and regulations.
According to directive 2012/19/EU, electronic
equipment must be recycled in a selective and
controlled way at the end of its useful life.