User Reference Manual - VI96 Display
1.19.3 Configuration for 'cnq. 2'
Configuration menu for mode ‘
counter quadrature
’ (‘
cnq.2
’).
Total impulses received are multiplied by the value of the ‘mul-
tiplier’ (‘
MuLt
’) register and divided by the ‘divider’ (‘
dIV
’) regis-
ter. Result is refreshed on the display.
• assign the value for parameter ‘
Multiplier
’ (‘
MuLt
’) from 1 to
999999.
• assign the value for parameter ‘
Divider
’ (‘
dIV
’) from 1 to
999999.
• assign the value for ‘
Preset
’ (‘
PrSt
’) from -199999 to 999999.
Reset activation loads on display the preset value.
• select the ‘
edges’
to count for each quadrature cycle (‘
q.124
’).
Select ‘
1--1
’ for 1 impulse per quadrature cycle. Select ‘
1--2
’ for
2 impulses per quadrature cycle. Select ‘
1--4
’ for 4 impulses per
quadrature cycle.
1.19.4 Configuration for 'cnl. 3'
Configuration menu for mode ‘
counter + inhibition control
’
(‘
cnI.3
’). Total impulses received are multiplied by the value of
the ‘multiplier’ (‘
MuLt
’) register and divided by the ‘divider’
(‘
dIV
’) register. Result is refreshed on the display.
• assign the value for parameter ‘
Multiplier
’ (‘
MuLt
’) from 1 to
999999.
• assign the value for parameter ‘
Divider
’ (‘
dIV
’) from 1 to
999999.
• assign the value for ‘
Preset
’ (‘
PrSt
’) from -199999 to 999999.
Reset activation loads on display the preset value.
• select the counting mode (‘
ModE
’) to ‘
uP
’ for upwards coun
-
ting (impulses received add) or ‘
doWn
’ for downwards counting
(impulses received substract).
• select the activation mode for the ‘
inhibition
’ (‘
Inh
’) control.
Select ‘
on_h
’ to inhibit the counting when channel B is at logical
state ‘1’. Select ‘
on_0
’ to inhibit the counting when channel B is
at logical state ‘0’.
1.19.5 Configuration for 'cnc. 4'
Configuration menu for mode ‘
counter + control add / subs
-
tract
’ (‘
cnc.4
’). Total impulses received are multiplied by the
value of the ‘multiplier’ (‘
MuLt
’) register and divided by the ‘di-
vider’ (‘
dIV
’) register. Result is refreshed on the display.
• assign the value for parameter ‘
Multiplier
’ (‘
MuLt
’) from 1 to
999999.
• assign the value for parameter ‘
Divider
’ (‘
dIV
’) from 1 to
999999.
• assign the value for ‘
Preset
’ (‘
PrSt
’) from -199999 to 999999.
Reset activation loads on display the preset value.
• select the activation mode for the ‘
control add / substract
’
(‘
Add
’). Select ‘
on_h
’ activates the addition of impulses recei-
ved on channel A when channel B is at logical state ‘1’ (impulses
on channel A substract if channel B is at logical state ‘0’). Select
‘
on_0
’ activates the addition of impulses received on channel
A when channel B is at logical state ‘0’ (impulses on channel A
substract if channel B is at logical state ‘1’).
Multiplier 1 to 999999
Divider 1 to 999999
Conf. counter
+ inhibition
Multiplier
Divider
Preset
Preset value
-199999 a 999999
Mode
Up
Down
Inhibition
Inhibits if
channel B is high
Inhibits if
channel B is 0 Vdc
Conf. counter
quadrature
Multiplier 1 to 999999
Divider 1 to 999999
Multiplier
Divider
Preset
Preset value
-199999 a 999999
Edges
1 imp. per cycle
2 imp. per cycle
4 imp. per cycle
Multiplier 1 to 999999
Divider 1 to 999999
Conf. counter
+ control add /
substract
Multiplier
Divider
Preset
Preset value
-199999 to 999999
Control S/R
Adds if channel
B is high
Adds if channel
B is 0 Vdc