Hohner Automaticos VI96 Скачать руководство пользователя страница 16

www.encoderhohner.com   -   [email protected]   -   Tel.: (00 34) 972 16 00 17

15

User Reference Manual - VI96 Display

1.19.11 Alarms

The ‘

Alarms

’ (‘

ALr

’) menu configures the independent activation 

of up to 3 relay outputs (or transistor or SSR modules), installed 

with the R1 optional modules (or T1 or SSR) 

(see section 2.1)

. For 

outputs up to 4 and 6 relays, see special modules R2, R4 and R6 

at section 

2.6

. The alarm states are indicated in the front display 

with leds marked as ‘1’, ‘2’ and ‘3’.
To configure an alarm, enter into the alarm menu (‘

ALr1

’, ‘

ALr2

’ 

or ‘

ALr3

’) and configure the following parameters :

• select ‘

Active

’ (‘

Act

’) to ‘

on

• at ‘

Alarm type

’ (‘

TypE

’) select the alarm to act as a maxi-

mum type alarm (‘

MAX

’) or a minimum type alarm (‘

MIn

’). The

maximum type alarm (or minimum type alarm) activates when

the display value is higher (or lower) than the setpoint value.

• at ‘

Setpoint

’ (‘

SEt

’) enter the value for the alarm activation

point

.

 This parameter is eligible for configuration through the

Fast access

’ menu 

(see section 1.19.12).

•  configure  the  hysteresis  value  at  ‘

Hysteresis

’  (‘

hySt

’).  The 

hysteresis applies to the deactivation process of the alarm. The 

alarm deactivates when the reading has passed the setpoint va-

lue plus the hysteresis value. Hysteresis helps to avoid repetiti-

ve switching of the alarm relays, due to fluctuating input signals 

around the setpoint.
• at ‘

Activation delay

’ (‘

dEL.0

’) configure the delay to apply

before  alarm  activation.  The  activation  delay  starts  counting

when the setpoint value is passed. Value from 0.0 to 99.9 se

-

conds.
• at ‘

Deactivation delay

’ (‘

dEL.1

’) configure the delay to apply

before alarm deactivation. The deactivation delay starts coun-

ting when the setpoint value plus the hysteresis value, is pas-

sed. Value from 0.0 to 99.9 seconds.

• to work with ‘windowed alarms’ (see graphical example be-

low) activate ‘

Setpoint

2

’ (‘

SEt2

’) to ‘

on

’ and then configure the 

desired second setpoint value. Second setpoint must always be 

higher in value than the first setpoint.

• the ‘

Relay inverted

’ (‘

r.Inv

’) parameter inverts the normal re-

lay connections. When set to ‘

on

’ the relay will be active when

alarm is inactive. For security applications where an inactive

relay controls the shutdown of the system.

• the ‘

Locked alarm

’ (‘

A.Lck

’) parameter disables the automa-

tic deactivation of the alarm. Alarm deactivation must be per-

formed manually, by pressing the ‘LE’ front button 

(see section 

1.19.14)

• the ‘

On  alarm

’  (‘

on.AL

’)  parameter  assigns  a  predefined

behaviour when alarm is activated. Select ‘

cont

’ to continue

counting. Select ‘

to_0

’ to load ‘0’ on displays. Select ‘

to_p

’ to

load preset value on display. Parameter ‘

dEL.1

’ is set to 1 se

-

cond when ‘

to_0

’ or ‘

to_p

’ are selected.

On alarm

Continue

To zero

To preset

Alarm 1

Setpoint

Hysteresis

Setpoint 2

Active

Alarm type

Alarms

Activation delay

Deactivation 

delay

Relay inverted

Locked alarm

Reading

Time

setpoint

hysteresis

Alarm as maximum, 

 

no hysteresis, no delays

on

off

Time

activation 

delay

on

off

deactivation 

delay

Time

Alarm as maximum, with 

hysteresis and delays

on

off

Time

Alarm as minimum, 

 

no hysteresis, no delays

Reading

Time

Setpoint 2

Setpoint 1

Alarm as minimum,

 

with double setpoint,

 

no hysteresis, no delays

on

off

Time

Содержание VI96

Страница 1: ...DISPLAY...

Страница 2: ...Trigger Sense 7 1 14 Function Cycler Counter 7 1 15 Slow Mode 8 1 16 Fast Mode 8 1 17 How to operate the menus 8 1 18 Message and errors 9 1 19 Configuration meny 10 1 19 1 Initial set up 10 1 19 2 Co...

Страница 3: ...8 1 21 Factory configuration 21 1 22 To access the instrumental 22 1 23 Modular system 22 1 24 Precautions on installation 23 1 25 Warranty 23 1 26 CE Declaration of conformity 23 2 OUTPUT AND CONTROL...

Страница 4: ...Independent alarms configurable as maximum or minimum with 1 or 2 setpoints per alarm hysteresis independent activation and deactivation delays and control for inverted relay Front protection IP65 Con...

Страница 5: ...ns with return to preset or reset to 0 genera te cycles of counting instrument counts from preset value to alarm value in never ending cycle The instrument provides memory of cycles counter Scalable r...

Страница 6: ...nections are indicated for a single sensor connected to the channel A For two sensors for inhibition control quadrature signal etc apply the same connection criteria also to channel B Note indicated v...

Страница 7: ...r L 11 to 60 Vdc and 24 48 Vac Isolation 2500 Veff with power H 1500 Veff with power L tested for 60 sec Consumption 1 5 W only meter 4 0 W meter with options Configuration 3 buttons front keypad Fron...

Страница 8: ...gger level is automatically configured when selecting a sensor from the Sensor Configuration SnSr Auto menu list The trigger level can be also manually modified from the SnSr TrIG menu entry The selec...

Страница 9: ...d by activating the Password PASS function While operating the configuration menu the alarm status is hold to the status they had before accessing the menu and the output and control modules remain in...

Страница 10: ...ns to the Func menu 5 The LE 3 key leaves the actual menu level and moves to the previous menu level 6 The LE 3 key leaves the configuration menu Changes are applied and saved at this moment 1 18 Mess...

Страница 11: ...E 3 key Configure the function mode selected cnF 2 to cnF 8 See sections 1 19 2 to 1 19 9 Configure the sensor at the SnSr menu See section 1 19 10 1 19 2 Configuration for cn 1 Configuration menu for...

Страница 12: ...ition Inh control Select on_h to inhibit the counting when channel B is at logical state 1 Select on_0 to inhibit the counting when channel B is at logical state 0 1 19 5 Configuration for cnc 4 Confi...

Страница 13: ...figure the nuMb parameter between 1 and 32 impulses See section 1 15 for more information on the SLoW mode in case of unstable signals activate the average filter AVr function It activates a recursive...

Страница 14: ...ng periods activate the SLoW parameter configuring the tIME parameter between 1 and 1000 seconds Configure the nuMb parameter between 1 and 32 impulses See section 1 15 for more information on the SLo...

Страница 15: ...h or by falling edge on_0 Activation for reset channel Act r configures the acti vation of the reset channel by rising edge on_h or by falling edge on_0 Excitation voltage V EXc configures the value o...

Страница 16: ...is passed Value from 0 0 to 99 9 se conds at Deactivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts coun ting when the setpoint value plus the h...

Страница 17: ...preset value configured 1 19 13 Super fast access If only a single function is selected for the fast access menu pressing the the UP 5 key will shortly display the function name and then automaticall...

Страница 18: ...menu is not password protected 1 19 20 Factory reset At the Factory reset FAct menu select yes to load the de fault factory configuration for the instrument see section 1 21 1 19 21 Firmware version T...

Страница 19: ...Multiplier 1 to 999999 Divider 1 to 999999 Multiplier Divider Preset Preset value 199999 a 999999 Edges 1 imp per cycle 2 imp per cycle 4 imp per cycle Conf counter inhibition Multiplier Divider Pres...

Страница 20: ...isabled Max waiting time Number of pulses Average filter SLOW mode Filter strength 0 disabled Espera m xima 1 a 1000 Seg Number of pulses Sensor NPN 2 wire Mechanical contact Namur Automatic conf NPN...

Страница 21: ...tpoint Hysteresis Setpoint 2 Active Alarm type Alarms Activation delay Deactivation delay Relay inverted Locked alarm Rising edge Falling edge Channel A activation Tools Key UP fast access Memory of m...

Страница 22: ...stor Pulls on reset pull up Trigger 2 5 Vdc Activation for channel A on rising edge on_h Excitation voltage 5 Vdc Antirrebound filter 0 mSeconds Tools Fast access Key UP off On Power Up Delay 0 second...

Страница 23: ...ront cover in front of the housing placing first corner X and then inserting clips A B C and D in this order Risk of electric shock Removing the front cover will grant access to the internal circuits...

Страница 24: ...nst all manufacturing de fects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse accident or manipu lation by non authorized personnel In case of malfunct...

Страница 25: ...uous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt 2 O...

Страница 26: ...gic Output The Analogic Output module provides 1 analog output with 4 20 mA or 0 10 Vdc configurable output range Output current loop configurable as active the instrument provides the exci tation for...

Страница 27: ...inal A A signal from RS 485 bus Terminal G GND Power Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G 2 5 Module RS 485 The RS 485 module provides a RS 485 communications module for VI96 of panel meters ASC...

Страница 28: ...modules are installed on slot Opt 1 and are con figured from instruments front keypad and provide setpoint configuration hysteresis independent activation and deactiva tion delays and second alarm set...

Страница 29: ...g Together with the KIP protector offer a full IP65 protection For VI96 of panel meters 4 1 Benchtop housing Benchtop housing for VI96 of panel meters Handle with three selectable positions Power conn...

Страница 30: ...www encoderhohner com info encoderhohner com Tel 00 34 972 16 00 17 29 User Reference Manual VI96 Display...

Отзывы: