Enclosure Alterations

Hoffman Enclosures Inc.

2100 Hoffman Way

Anoka, MN 55303

1745

(763) 422

2211

www.hoffmanonline.com

Hoffman cannot assure the safety or effectiveness of any alterations or

additions not made by Hoffman Enclosures Inc.  However, the following

information may be helpful.  These instructions do not eliminate the need

to consult with equipment manufacturers and to observe all regulatory agency procedures and safe

practices to assure the proper electrical and mechanical function of Hoffman products in each

particular application.

1.  REPAINTING

See “Instructions for Repainting Hoffman

Standard Paint Finishes”, part number

23155002.

2.  MOUNTING INSTRUCTIONS

  a.  Wall mounted enclosures have either an

internal mounting means or external

mounting feet.  Proper fasteners must be

used in all mounting holes to secure the

enclosure to the wall.

  b.  Floor mounted enclosures have floor

stands (legs) which include mounting

plates.  Proper fasteners must be used in

all mounting holes to securely anchor the

enclosure to the floor.

3.  DOOR CLOSING ADJUSTMENTS

  a.  Single door (wall mounted)

If the surface on which the enclosure is

mounted is not flat, the door may not open

and close properly.  Also, if heavy

equipment is mounted on a large door, the

door may sag slightly.  If the top of the door

strikes the lip which extends around the

body opening, place metal shims behind

the mounting foot which is located at the

bottom of the enclosure and closest to the

door hinge.  Place the shims between the

mounting foot and the wall or mounting

surface.  Be sure all mounting screws are

tightened securely.

  b.  Two door (floor mounted)

The overlapping doors are factory

fitted to

meet evenly at the top and bottom.  If the

floor under the enclosure is not level, the

doors will not close evenly.  In this case,

place metal shims under the corners of the

enclosure.  The enclosure should be

bolted in place with the doors closed to

prevent tipping when installing shims.

Shims under the right front corner will raise

the right door.  Shims under the left front

corner will raise the left door.  It is

important that the doors meet evenly to

insure a proper seal against liquids and

dust.  Be sure all mounting bolts are

tightened securely.

4.  PANEL INSTALLATION

When the interior panel is being installed, it

may be necessary to bend one or more

mounting studs slightly to permit the panel to fit

in place.  Simply position the panel on the studs

that line up properly and pry the other studs

into position with a suitable screwdriver

inserted through the panel holes.

5.  REMOVING HINGE PINS FROM

CONTINUOUS HINGES

This can be a difficult operation requiring one or

more people.  This procedure is best

accomplished by using a small diameter punch

to drive the hinge pin toward the bottom of the

enclosure.  Lay the wall

mounted and

floor

mounted or free

standing enclosure on

its back side (see note 7 below).  When the

hinge pin protrudes about two inches below the

bottom hinge barrel, bend the end of the pin

180

°

 so it is shaped like the letter “J”.  Use an

electric or air powered vibrating hammer fitted

with a tool which has a hole in the end to fit

over the hinge pin, and drive the hinge pin out

while opening and closing the door.  To install

the hinge pin, straighten the pin and drive it in

with the vibrating hammer while opening and

closing the door.  Most hinge pins have one

end chamfered, so be sure to start the

chamfered end first when installing the pin.

6.  PRINT POCKET

The print pocket on the door can be inverted or

removed entirely.

7.  LIFTING ENCLOSURES BY EYEBOLTS

To lift an enclosure which has eyebolts or

mounting feet, be sure to use all the eyebolts

and top mounting feet provided.  Arrange the

chains and cables with spreader bars so you

are lifting straight up on the eyebolts or top

mounting feet.

87569073

Rev. B  110539

P/N 99401677

E

 2004 Hoffman Enclosures Inc.

®

Содержание 99411400

Страница 1: ...1 4 20x7 8 bolt through the hole in the panel as shown 2 Secure bolt with keps nut The keps nuts must penetrate into the paint to insure electrical continuity 3 Attach the ground wire and secure with...

Страница 2: ...00 Grounding Label Keps Nut 1 4 20 Hex Nut Ground Wire not included 1 Secure keps nut on each ground stud The keps nuts must penetrate into the paint to insure electrical continuity 2 Attach the groun...

Страница 3: ...Disconnect Devices And For Flexible Cable Disconnect Devices In Hoffman Bulletin A25 Wall Mounted Disconnect Enclosures 3 Point Latching 2 Point Latching 87569072 Rev B 113357 P N 99401665 E 2005 Hoff...

Страница 4: ...ion Index Brand of Disconnect Type Variable Depth Flexible Cable See Pages 6 7 16 17 Variable Depth Variable Depth Variable Depth Flexible Cable Flexible Cable Flexible Cable 4 5 8 9 10 11 12 13 14 15...

Страница 5: ...ch deep enclosures and the bottom holes for twelve 12 and sixteen 16 inch deep enclosures Note 4 Hoffman enclosures include a latch bar and have a door catch and stud type standoffs provided on the do...

Страница 6: ...Inc 4 87569072 Wall Mounted Disconnect Enclosures Installation Instructions for Allen Bradley 1494V variable depth Disconnects Figure 3 E 4 75 for 8 00 Deep E 7 09 for 10 00 Deep E 11 62 for 12 00 De...

Страница 7: ...1 38 1 09 4 50 1 38 1 09 136 8 32 UNF 1494V M50 for 15 150 AMP West Do Not Install Do Not Install 10 94 1 38 1 25 7 25 1 38 1 25 69 2 03 10 62 201 1 4 20 UNC 1494V M60 for 70 400 AMP West Do Not Inst...

Страница 8: ...igure 3 E 4 75 for 8 00 Deep E 7 09 for 10 00 Deep E 11 62 for 12 00 Deep E 11 62 for 16 00 Deep Hole Pattern For Disconnect Switch Size C361NC C361SC 30 AMP C361ND C361SD 60 AMP C361NE C361SE 100 AMP...

Страница 9: ...NC HMCP FS FH EHD FDB FD HFD 150A 3 91 6 26 10 79 2 62 4 50 1 38 8 32 UNF JS JH JL 250A 6 22 10 75 3 13 7 25 1 38 31 6 95 2 75 10 32 UNF HMCP 250A 6 22 10 75 3 13 7 25 1 38 31 6 95 2 75 1 4 20 UNC KH...

Страница 10: ...7569072 Wall Mounted Disconnect Enclosures Installation Instructions for General Electric Type STDA Variable Depth Operating Mechanisms Figure 3 E 4 75 for 8 00 Deep E 7 09 for 10 00 Deep E 11 62 for...

Страница 11: ...ot Install 6 91 1 34 3 35 5 51 AND 12 20 SDOM1A TEB TED 4 1 4 20 2 50 3 97 8 50 75 3 00 6 75 SDOM1A SDOM1AP TB1 TEC TECL 4 1 4 20 2 50 3 97 8 50 75 3 00 6 75 TDOM3 TFJ TFK 4 1 4 20 3 97 8 50 1 69 2 75...

Страница 12: ...nc 10 87569072 Figure 3 Wall Mounted Disconnect Enclosures Installation Instructions for Square D 9422 Variable Depth Operating Mechanisms E 4 75 for 8 00 Deep E 7 09 for 10 00 Deep E 11 62 for 12 00...

Страница 13: ...tall Do Not Install 6 88 1 31 9 44 8 00 RG1 4 1 2 3 4 8 32 2 25 4 59 9 13 1 47 1 18 3 94 RN1 4 1 2 3 4 8 32 2 78 5 13 9 66 1 38 1 50 5 13 RP1 4 1 2 3 4 10 24 2 78 5 13 9 66 1 56 1 50 7 13 RR 1 4 1 2 3...

Страница 14: ...E 2005 Hoffman Enclosures Inc 12 87569072 Figure 3 CH Wall Mounted Disconnect Enclosures Installation Instructions for Cutler Hammer C371 Flex Shaftt Flexible Cable Operating Mechanisms...

Страница 15: ...ct Enclosure Description Enclosure Depth H 8 00 3 25 A25 Wall Mounted Disconnect Enclosure 10 00 5 59 A25 Wall Mounted Disconnect Enclosure 12 00 10 13 16 00 10 13 Step1 Determine disconnect hole patt...

Страница 16: ...E 2005 Hoffman Enclosures Inc 14 87569072 Figure 3 GE Wall Mounted Disconnect Enclosures Installation Instructions for General Electric SCH Flexible Cable Operating Mechanisms...

Страница 17: ...16 18 2 75 14 25 2 75 TABLE 2 Bulletin Hoffman Disconnect Enclosure Description Enclosure Depth C H 8 00 3 25 A25 Wall Mounted Disconnect Enclosure 10 00 5 59 A25 Wall Mounted Disconnect Enclosure 12...

Страница 18: ...E 2005 Hoffman Enclosures Inc 16 87569072 Bulletin A25 Wall Mounted Disconnect Enclosures Installation Instructions for Siemens I T E Max Flext Flexible Cable Operating Mechanisms Figure 3 ITE...

Страница 19: ...HOF036 4 1 4 20 1 50 7 50 1 50 FHOJ036 4 1 4 20 2 50 9 75 2 50 FHOLM036 4 1 4 20 2 50 9 75 2 50 These mechanisms include 36 operating cables If longer cables are needed order I T E components separate...

Страница 20: ...E 2005 Hoffman Enclosures Inc 18 87569072 Figure 3 SQ D Wall Mounted Disconnect Enclosures Installation Instructions for Square D 9422 Flexible Cable Operating Mechanisms...

Страница 21: ...25 See Square D instructions for range of C dimension which vary for 36 60 and 120 cable lengths See Square D instructions for relationship between 1 4 20 and 375 diameter holes for LA circuit breake...

Страница 22: ...reat Britain Schroff UK Ltd Maylands Avenue Hemel Hempstead Herts HP2 7DE 44 01442 240471 www schroff co uk Sweden Schroff Scandinavia AB Box 2003 12821 Skarpn ck 46 08683 61 00 www schroff se France...

Страница 23: ...s of the enclosure The enclosure should be bolted in place with the doors closed to prevent tipping when installing shims Shims under the right front corner will raise the right door Shims under the l...

Страница 24: ...enabling multiple padlocks to be installed on a de energized switch Touch up paint is used to repair the finish of enclosures and panels Window kits are available for many types of Hoffman enclosures...

Отзывы: