NIL Hoffman Enclosures Inc.
Wall
−
Mounted Disconnect Enclosures
Installation Instructions for Square D 9422
Flexible Cable Operating Mechanisms
TABLE 1
Sub
−
Panel Drilling
Cable
Mechanism
Disconnect
Mechanism
No. of Holes
Hole Position
Hole Size
X
Y
C
min*
TCN, TCF
4
1,4,6,7
10
−
24
5.50
4.50
1.00
CFT
TDN, TDF
4
1,4,6,7
10
−
24
5.50
4.50
1.00
CFT
TEN, TEF
4
1,4,6,7
10
−
24
5.50
4.50
1.00
CGJ
GJL
4
1,2,3,4
8
−
32
1.18
3.94
2.50
CFA
FAL, FHL
4
1,2,3,4
8
−
32
1.50
5.13
3.75
CKA
KAL, KHL
4
1,2,3,4
10
−
24
1.50
7.13
3.75
CLA**
LAL LHL
4
1,2,3,4
1/4
−
20
6.63
6.56
2.25
CLA**
LAL, LHL
4
1,2,3,4
.375 Dia.
2.00
9.25
−
−
−
* See Square “D” instructions for range of “C” dimension which vary for 36”, 60” and 120” cable lengths.
** See Square “D” instructions for relationship between 1/4
−
20 and .375 diameter holes for LA circuit breaker.
TABLE 2
Bulletin
Hoffman Disconnect Enclosure Description
Enclosure Depth
H
8.00
3.25
A25
Wall Mounted Disconnect Enclosure
10.00
5.59
A25
Wall Mounted Disconnect Enclosure
12.00
10.13
16.00
10.13
Step1
−
Determine disconnect hole pattern from Figure 3 SQ. D and the above tables. See disconnect manufacturers
instructions for range of disconnect location based on cable length being used and depth of enclosure.
NOTE
−
Locate disconnect so appropriate wire bend space is provided for the line side wire size being used. Refer
to National Electrical Code Article 430
−
10b for wire bend space required.