INSTALLATION
This section provides instructions for connecting cables, mounting, and testing the 16 Channel I/O Panel Module
for installation.
q
Using Loop Explorer 2, add the panel module to the existing configuration and configure it as required for the
system. For detailed information on the configuration settings, refer to the
section.
q
Notify the monitoring center and location security that the FireNET L@titude Fire Alarm Control Panel will be
temporarily out of service.
q
Remove the module from its packaging and check its contents.
q
Set the address of the module as configured in Loop Explorer 2. Refer to
for details.
q
Determine the slot (E or higher) where the panel module will be installed and place the provided sticker label on the
corresponding field terminals.
q
Connect field wiring as shown in the
section below.
q
Transfer the new configuration from Loop Explorer 2 into the panel.
q
Wait for the "Sending configuration to panel" (in LE2) and "Saving configuration" (on the panel) steps to complete.
q
Remove AC and battery power from the panel.
q
Remove the black plastic cover.
q
Install the module into selected slot on the Main Back Board or an Extension Board of the panel.
q
Restore AC and battery power.
q
Wait for the panel start-up process to complete. Refer to the
FireNET L@titude Fire Alarm Control Panel
Installation Manual (MAN-1431HA)
for more information.
q
Test communication from the panel via the
q
Resolve any troubles related to the new connections.
q
Activate each circuit and verify that all connected devices function properly.
q
Replace the black plastic cover.