![Hochiki S772 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/hochiki/s772/s772_information-manual_2143422007.webp)
OVERVIEW
16 Channel I/O Panel Module (S772)
The 16 Channel I/O Interface enhances the versatility of the alarm system by providing additional input and
output capabilities to the FireNET L@titude Fire Alarm Control Panel. Inputs and outputs can be selected for up
to 16 individual channels. All inputs and outputs are configured in the same way as devices connected to
addressable loops of the panel. The 16 Channel I/O Interface can be configured to contribute or act upon cause
and effect logic.
Use Case Examples
The 16 Channel I/O Interface can be used to interface the L@titude panel to a NAC extender or Voice
Evacuation system, by providing
l
inputs to the L@titude panel for dry contact closures such as General Trouble, AC Power Trouble, or Battery Trouble
from these devices.
l
outputs from the panel to control various NAC or Voice Evacuation outputs.
The 16 Channel I/O Interface can be used to interface the L@titude panel to a secondary panel or releasing
panel, by providing
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 | March 2021 | MAN-1420HA
Page 7
Overview