Troubleshoot ing | 29
Trouble Message
Description
both links. In this case, the panel will show multiple instances of this trouble; one for each other
panel on the network.
Network Node Double Addressed
This event indicates that more than one panel on the network has the same node number. This
is a configuration error, and should never occur once the network has been properly configured.
Full Short Circuit Trouble
This event indicates that a short circuit has been detected by the link impedance
measurement. This indicates a wiring error, or damage to the wires connecting the panel to its
neighbor.
Full Open Circuit Trouble
This event indicates that an open circuit has been detected by the link impedance
measurement. This indicates a wiring error, or damage to the wires connecting the panel to its
neighbor. The following two troubles are optional, and are not included in the default firmware
build.
Partial Short Circuit Trouble
This event indicates that the link impedance measurement has detected an impedance below
the normally expected range.
Partial Open Circuit Trouble
This event indicates that the link impedance measurement has detected an impedance above
the normally expected range.
Version 1.04 | May 2019 | MAN-1432HA
Содержание FIRENET L@TITUDE
Страница 1: ...FIRENET L TITUDE FIRE ALARM CONTROL PANEL OPERATING INSTRUCTIONS Version 1 04 May 2019 MAN 1432HA...
Страница 7: ...InterpretingPanel Information 7 Version 1 04 May 2019 MAN 1432HA...
Страница 11: ...User Access Levels 11 Version 1 04 May 2019 MAN 1432HA...
Страница 12: ...Controls 12 Version 1 04 May 2019 MAN 1432HA CONTROLS No User Group...
Страница 13: ...Controls 13 System Information Version 1 04 May 2019 MAN 1432HA...
Страница 23: ...Controls 23 Version 1 04 May 2019 MAN 1432HA...
Страница 27: ...General Information 27 Version 1 04 May 2019 MAN 1432HA...