General Informat ion | 26
Version 1.04 | May 2019 | MAN-1432HA
GENERAL INFORMATION
Operating Instructions
These operating instructions shall be placed near the panel.
Inspecting Batteries
Inspect the standby batteries annually to determine the connection integrity to the FireNET L@titude Fire Alarm
Control Panel. The fire control panel contains sealed lead acid batteries to provide standby power in the event of power
failure. The standby batteries have a life expectancy of 3 to 5 years. Test the standby batteries annually in accordance
with the battery manufacturer’s recommendations to determine their suitability for continued standby operation.
Replacing Standby Batteries
Replace standby batteries when the service period reaches 3 to 5 years or when the low battery message is present on
LCD display. The standard size cabinet of the panel accepts battery sizes up to 28 Ah. Batteries larger than 28 Ah may
be mounted remotely in a UL listed battery cabinet. Batteries smaller than 28 Ah do not require special cabinet mounting
considerations. The 5.25 A power supply charges up to 60 Ah; the 10.25 A power supply charges up to 100 Ah.
Related Documentation
The following document shall be used to provide additional information for installing and operating the FireNET L@titude
Fire Alarm Control Panel:
FireNET L@titude Alarm Control Panel Installation Manual (MAN-1431HA)
Содержание FIRENET L@TITUDE
Страница 1: ...FIRENET L TITUDE FIRE ALARM CONTROL PANEL OPERATING INSTRUCTIONS Version 1 04 May 2019 MAN 1432HA...
Страница 7: ...InterpretingPanel Information 7 Version 1 04 May 2019 MAN 1432HA...
Страница 11: ...User Access Levels 11 Version 1 04 May 2019 MAN 1432HA...
Страница 12: ...Controls 12 Version 1 04 May 2019 MAN 1432HA CONTROLS No User Group...
Страница 13: ...Controls 13 System Information Version 1 04 May 2019 MAN 1432HA...
Страница 23: ...Controls 23 Version 1 04 May 2019 MAN 1432HA...
Страница 27: ...General Information 27 Version 1 04 May 2019 MAN 1432HA...