background image

Testifire 1000 or 2000 with TS3 or TC3:

1.

Insert the battery baton, hold the Testifire head unit by the
handle and depress the upper spring button on the battery
baton. Align the button with the location hole in the handle

and push the battery baton into the handle until the button
springs up through the location hole.

2.

Insert the other end of the battery baton into the Solo

access pole and depress the lower spring button. Align it
with the location hole and push the battery baton further
into the pole until the button springs up through the hole.

3.

Remove the capsule from its outer carton and Anti-Static
bag.

4.

Remove the spring clip protector cap from the new

capsule.

5.

Holding the capsule by spring clips with the label on the
underside, carefully insert the new capsule into the

capsule port. Push it into position, ensuring that the clips
spring out positively on both sides of the capsule.

6.

Close the access cover securely.

7.

Program the tester to the following options available:

Smoke, Heat or CO.

8.

Raise Testifire over the sensor. The sensor should touch

the base of the inner clear cup.

9.

Lower Testifire from the sensor.

Testifire's LED Indications:

Blue Solid:

Smoke test in progress

Red Solid:

Heat test in progress

Green Solid:

CO test in progress

Green Slow Flashing:

Standby mode

Green Fast Flashing:

Operational mode

Red Flashing:

Battery needs charging, 
but still operational

Alternating Red/Green Flashing: Timeout indication (after 

         2 minutes of continuous 
         testing on one stimulus or 
         combination of stimuli

Red Solid:

Error

Green Solid:

CO cooling

Alternating Red/Green

CO cooling phase wait 

         until standby mode status 
         before continuing to test CO

The Hochiki ACD-V is a Multi Criteria Sensor. The ACD-V is
capable of Smoke, Heat and CO Detection individually along
with many criteria combinations based upon the activation

mode setting of the detector (the activation mode is set through
panel programming). To perform the detector test(s), the
sensor must first be placed in an individual Activation Mode

single criteria activation mode may or may not be the normal

sensor testing has been completed; it is essential that the
activation mode be restored to the original setting.

Prior to testing any sensor, care should be exercised to ensure
proper disabling of live signals and notification circuits of the

may result in false alarm signals which could place life and

To view or alter Activation Modes on the FireNET series of

Panels (Please consult your manufacture for other panels):

Enter Level 2 password or Insert "Enable Access" Key >Turn
Key to right. You are Now in Access Level 2.

Arrow Button down to Access Level 3.

Enter Level 3 password: _ _ _ _

on Loop: Select ACD-V (Enter) > Edit Modes > Select:

DAY:
NIGHT:

Using the Testifier 2000, all three Criteria of the Sensor can be

tested individually.

Restore activation mode of sensor to original setting

JULY 2016

Pg 5 of 6

Analog 2 

Содержание ALN-V

Страница 1: ...Technical Bulletin Analog 2 JULY 2016...

Страница 2: ...une to noise The control panel is able to verify the status of any device Whether the device is dirty or approaching an alarm condition it can make this determination routinely It is possible to assig...

Страница 3: ...duce the effective range of the sensors Such obstruction should designate a new separation point and be considered a border for a new section 4 Beams or other obstructions extending more than 8 but le...

Страница 4: ...our left hand and grasp the chamber cover with your right hand Twist the chamber cover counter clockwise until the Cover Tabs clear the Tab lock Lift and seperate the chamber cover from the optical un...

Страница 5: ...ol CRT Remove Disassemble the Sensor 1 Place the sensor to be disassembled on the CRT as shown 2 Push the CRT The sensor will automatically pop open 3 The contact blades on the sensor will engage on t...

Страница 6: ...g Battery needs charging but still operational Alternating Red Green Flashing Timeout indication after 2 minutes of continuous testing on one stimulus or combination of stimuli Red Solid Error Green S...

Страница 7: ...gray button to switch programmer to on A battery check message will appear followed by the device address un programmed sensors will read a default address of 127 or 255 3 Set the required address by...

Страница 8: ...t gray button to switch programmer to on A battery check message will appear followed by the device address un programmed sensors will read a default address of 127 or 255 3 Set the required address b...

Отзывы: