24VDC CLEAR Lens Indoor Strobe Current Ratings
HEC24 and
HES24 Series
Available
Candela
HEC3-24 and
HES3-24 Series
Available
Candela
Strobe
Candela
Regulated
24VDC Max.
Operating
Current(mA)
Regulated
24VFWR Max.
Operating
Current (mA)
15
42
77
15/75
67
113
30
58
102
60
97
161
75
116
225
110
161
256
177
213
341
WHEC24 AND WHES24 PRODUCT INFORMATION
NOTICE
: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS
PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110%
OF THIS RANGE FOR SYSTEM OPERATION.
12VDC CLEAR Lens Strobe Current Ratings
Use with HEC3-12 and HES3-12 Products
Candela
Regulated
12VDC Max.
Operating
Current (mA)
Regulated
12VFWR Max.
Operating
Current (mA)
15
92
145
30
141
224
60
260
459
75
312
460
NOTICE
: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE
RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED
TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80%
AND 110% OF THIS RANGE FOR SYSTEM OPERATION.
24VDC CLEAR Lens Outdoor
Strobe Current Ratings
Use with WHEC24 and WHES24 Products
Candela
Regulated 24VDC
Max. Operating
Current (mA)
Regulated
24VFWR Max.
Operating
Current (mA)
75
170
263
Horn Decibel Levels
Horn Current Ratings Over
Input Voltage Range of 16-33V
Horn Mode
Minimum SPL
at 10Ft. Per
ANSI/UL 464
(HIGH)
Minimum SPL
at 10Ft. Per
ANSI/UL 464
(LOW)
Regulated 24VDC
Max. Operating
Current (mA)
HIGH Setting
Regulated 24VFWR
Max. Operating
Current (mA)
HIGH Setting
Temp 3 2400Hz
78 dBA
71* dBA
28
48
Temp 3 Mechanical
76 dBA
70* dBA
25
44
Temp 3 Chime
70* dBA
66* dBA
15
30
Continuous 2400Hz
81 dBA
74* dBA
28
48
Continuous Mechanical
80 dBA
72* dBA
25
44
Continuous Chime
70* dBA
66* dBA
15
30
Whoop
82 dBA
69* dBA
56
62
HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION
Horn Decibel Levels
Horn Current Ratings Over
Input Voltage Range of 8-17.5V
Horn Mode
Minimum SPL
at 10Ft. Per
ANSI/UL 464
(HIGH)
Minimum SPL
at 10Ft. Per
ANSI/UL 464
(LOW)
Regulated 12VDC
Max. Operating
Current (mA)
HIGH Setting
Regulated 12VFWR
Max. Operating
Current (mA)
HIGH Setting
Temp 3 2400Hz
76 dBA
69* dBA
29
48
Temp 3 Mechanical
75 dBA
68* dBA
26
45
Temp 3 Chime
62* dBA
60* dBA
13
24
Continuous 2400Hz
79 dBA
74* dBA
29
48
Continuous Mechanical
78 dBA
72* dBA
26
45
Continuous Chime
63* dBA
61* dBA
13
24
Whoop
78 dBA
71* dBA
55
61
NOTICE:
THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.
THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING. WHILE THE HORN
IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINUOUS MODE. UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93%
HUMIDITY.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level required for public mode fire protection service. These settings are acceptable
only for private mode fire alarm signaling use. Use the high dBA setting for public mode applications (the chime tone is always private mode).
550-0534
Page 2
NOTICE:
DC VOLTAGE RANGE LIMITS: 8-17.5V. THIS
PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE
RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE
FOR SYSTEM OPERATION.
CAUTION:
Strobe light must
be installed within
16 feet of the
pillow when used
in a sleeping area.
**Effective Intensity Requirements
for Sleeping Areas
Visible Notification Appliance
Distance from Ceiling to Top of Lens
Intensity
greater than or equal to 24"
110cd
less than 24"
177cd