I. INTRODUCTION

The Hochiki America models HEC24, HES24, HEH24, HEH12, HEC3-24, HES3-24, HEC3-12, HES3-12, WHEC24, WHES24 are high quality audible and/or visible signaling appliances. The

high intensity strobe utilizes a Xenon flash tube that generates a high-intensity flash visible from all angles. This appliance is intended to provide a visible, audible or audible/visible, depending

on the model, notification signal for the purpose of life safety and property protection. The HEC3-24, HES3-24, HEC3-12, HES3-12 are provided with a slider switch which allows for candela

selection at the installation site; the candela intensities which can be selected are 15Cd, 30Cd, 60Cd, 75Cd, or 110Cd (24VDC only). The HEC24 and HES24 are fixed candela units; the

candela intensities which can be ordered, are 177Cd and 15/75Cd. The WHEC24 and WHES24 are fixed candela units, available in a 75 candela intensity only. This appliance is ideal for any

occupancy that requires notification appliances per the applicable building or fire code or wherever dependable alarms are required.

The HEC24, HES24, HEC3-24, HES3-24, HEC3-12, HES3-12 strobe is listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired (The 15/75Cd model on the

HEC24 and HES24 is additionally listed in compliance with ANSI/UL1638). The WHEC24 and WHES24 strobe is listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private

Mode Emergency and General Signaling.

II. LOCATION

This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA

documents that provide standards on notification appliances for protective signaling systems. The HEC24, HES24, HEH24, HEH12, HEC3-24, HES3-24, HEC3-12, HES3-12 are intended for

indoor installations only; this appliance is

not

listed for

outdoor

or drip proof applications. The WHEC24 and WHES24 are intended for indoor or outdoor installations; this appliance is rated for

outdoor or drip proof applications when used in conjunction with the HGOE Enclosure.

Wall mounted strobe and horn/strobe appliances shall have their entire lens at heights above the finished floor of not less than 80 in. (2m) and not greater than 96 in. (2.4m)**. Spacing shall be

in accordance with Table A. If a room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used. Wall mounted

horn only appliances shall have their tops above the finished floors at heights of not less than 90 in. (2.30m) and below the finished ceilings at heights of not less than 6 in. (152mm). Different

mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met.

III. MOUNTING, ROUGH-IN BOX AND RUN WIRING

This unit is designed for mounting to most single gang boxes, 4" square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes. Conduit entrance to boxes should be

selected to insure sufficient wiring clearance.

1. Run a minimum 18 gauge insulated 2 or more conductor cable.

2. Mount a box for each remote signaling appliance. Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block receptacle. Place housing over

mounted assembly and screw together with single screw at the bottom of the signal. Cover screw with plastic tab.

NOTICE:

WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL. INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS

TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN, ONLY ONE OF

THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM

BEING PLACED UNDER THE SAME TERMINAL.

550-0534

Page 1

Strobe light can not be seen when objects such as doors,

furniture or walls block strobe light.

NOTICE:

THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE

OCCUPANT IN ORDER TO BE SEEN.

VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD

OF ALERTING THE HEARING IMPAIRED. VISUAL SIGNALS MAY NOT BE

THE PREFERRED METHOD FOR NOTIFYING ALL HEARING IMPAIRED

INDIVIDUALS.

THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE

PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED

BY VISUAL, THE STROBE WILL NOT BE EFFECTIVE.

NA = Not allowable

Table A

Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2010 Edition

Maximum Room Size

Minimum Required Light Output ( Effective Intensity, Cd)

Meters

Feet

One Light

per Room

Two Lights per

Room (Located on

Opposite Walls)

Four Lights per Room

(One Light per Wall)

6.10 x 6.10

20 x 20

15

NA

NA

8.53 x 8.53

28 x 28

30

Unknown

NA

9.14 x 9.14

30 x 30

34

15

NA

12.2 x 12.2

40 x 40

60

30

15

13.7 x 13.7

45 x 45

75

Unknown

19

15.2 x 15.2

50 x 50

94

60

30

16.5 x 16.5

54 x 54

110

Unknown

30

16.8 x 16.8

55 x 55

115

Unknown

28

18.3 x 18.3

60 x 60

135

95

30

19.2 x 19.2

63 x 63

150

Unknown

37

20.7 x 20.7

68 x 68

177

Unknown

43

21.3 x 21.3

70 x 70

184

95

60

24.4 x 24.4

80 x 80

240

135

60

27.4 x 27.4

90 x 90

304

185

95

30.5 x 30.5

100 x 100

375

240

95

33.5 x 33.5

110 x 110

455

240

135

36.6 x 36.6

120 x 120

540

305

135

39.6 x 39.6

130 x 130

635

375

185

HEC24/HES24/HEC3-24/HES3-24/HEC3-12/HES3-12 PRODUCT INFORMATION

Содержание HEC24 Series

Страница 1: ... horn only appliances shall have their tops above the finished floors at heights of not less than 90 in 2 30m and below the finished ceilings at heights of not less than 6 in 152mm Different mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met III MOUNTING ROUGH IN BOX AND RUN WIRING This unit is designed for mounting to most single gang ...

Страница 2: ...nuous Chime 70 dBA 66 dBA 15 30 Whoop 82 dBA 69 dBA 56 62 HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION Horn Decibel Levels Horn Current Ratings Over Input Voltage Range of 8 17 5V Horn Mode Minimum SPL at 10Ft Per ANSI UL 464 HIGH Minimum SPL at 10Ft Per ANSI UL 464 LOW Regulated 12VDC Max Operating Current mA HIGH Setting Regulated 12VFWR Max Operating Current mA HIGH Setting Temp 3 2400H...

Страница 3: ...e lights will NOT be synchronized Place switches 1 and 2 in the ON position on the HEC24 HEC3 24 HEC3 12 WHEC24 to power both the audible and visible from a single pair of power wires If you wish to power the horn and strobe from independent sources of power place switches 1 and 2 in the OFF position on the HEC24 HEC3 24 HEC3 12 WHEC24 and connect power to the appropriate terminals CAUTION When us...

Страница 4: ...h laws regulations and rules to particular fact patterns Each person s activities can differently affect the obligations that exist under applicable laws regulations or rules Therefore these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice Hochiki America will not be responsible for any action or failure to act in...

Отзывы: