25
Figure 17 Installation under a sloped ceiling
9.5. Installation in a monitor roof
The installation for a monitor roof should be performed as in Figure 18. The detector's
installation height should be 0.8H or higher. If there is a ventilation in the top part of the
roof then the detector must be placed below the opening. The detector should be installed
in accordance with the following height restriction : H-a
>
h
≥
0.8H
Figure 18 Installation in a monitor roof
9.6. Installation in corridors or aisles
9.6.1. Closed corridor
When the detector is installed in a corridor with a closed corner it is possible to use just
one detector as shown in Figure 19 providing that the distance L is less than 23’.