d. Rectifier
A diode-bridge rectifier (9) receives 400-Hz AC from phase C of the generator output and converts it
to a pulsating, direct current for energization of the load contactor holding coil only. This DC
coil-holding circuit is controlled indirectly by controlling the 400-Hz AC to the rectifier. The ground
circuit for the rectifier’s AC supply must pass through the relay contacts in the protective monitor
module to ground cable N. Therefore, any time a protective device functions to open the protective
monitor relay, the rectifier’s AC circuit is opened. No DC is then available for the load contactor
holding coil, hence, the load contactor opens.
2
3
4
2
4
5
9
1
7
8
6
3
6
3
6
1. Overload PC Board
2. Resistor, 50 ohm, 20 watt (R16, R17, R18)
3. Line Drop Current Transformer (T4, T5, T6)
4. Resistor, 16.6 ohm, 20 watt (R33, R34, R35)
5. Load Contactor
6. Overload Current Transformer (T30, T31, T32)
7. Flyback Diode, Exciter
8. Resistor, 100 ohm, 25 watt, No. 1 Contactor
9. Rectifier, No. 1 Contactor (CR6)
Single Output Power Module
Figure 9
OM-2084 / Operation and Maintenance Manual
90CU24 / Series 500392 Generator Sets
November 27/1997
Chapter 1-1
Page 19
Содержание 90CU24
Страница 193: ......
Страница 194: ......
Страница 195: ......
Страница 196: ......
Страница 197: ......
Страница 198: ......
Страница 199: ......
Страница 200: ......
Страница 201: ......
Страница 202: ......
Страница 203: ......
Страница 204: ......
Страница 205: ......
Страница 206: ......
Страница 207: ......
Страница 208: ......