Generator Excitation Circuits
Trouble, Symptom
Test, Check, And/or
and Condition
Probable Cause
Remedy
No (or low) generator output
voltage in all phases.
Generator operating at 400 Hz
(continued).
e.
Defective connector at
voltage regulator, or
defective wiring from
regulator to exciter field
Disconnect plug from voltage
regulator PC board. Using
jumper leads with clip and prod
terminals, connect 12-V DC to
terminals 1 and 4 in loose plug.
Connect NEGATIVE to terminal
4 Connect POSITIVE lead to
terminal 1 (see Schematic and
Connection Diagrams in Chapter
5). If generator will NOT
produce at least 80 V-AC,
replace or repair connector and
wiring between voltage regulator
and exciter field as required.
OM-2084 / Operation and Maintenance Manual
90CU24 / Series 500392 Generator Sets
Chapter 2-4
November 27/1997
Page 14