
·
The recommended cable size for 28.5 volt DC is determined by the maximum starting load
amperage expectations. A maximum starting load of 1500 amps. requires two single
conductor 4/0 cables. A maximum starting load of 600 amps. requires two single
conductor 2/0 cables.
NOTE: Some operators may wish to add a second cable assembly with MS-25019 plug connector for
starting aircraft such as Jetstar and Sabre liner.
(2)
Cable connection (See Figure 1)
·
Open and remove the right rear door and the panel below the door. Set aside.
·
Loosen the output cable clamp and thread the lugged end of the output cable through the
opening in the right side of the unit.
·
Connect the POSITIVE cable lead to the output terminal on the contactor. Connect the
NEGATIVE cable lead to the negative output terminal located above the load contactor.
ALWAYS place the lead under the flat washer shown.
Chapter 1-2
November 1, 2000
Page 2
OM-2094 / Operation and Maintenance Manual
Jet-Ex 5D / Series 500285 / Generator Set
Positive Cable Connection
Negative Cable Connection
Output Cable Connections
(Right Side of Unit)
Figure 1
To Order Parts Call 1-888-702-5326 - https://monsterfloorequipmentparts.com