OM-950 Page 16
4-8. Connecting Input Power
802 246-A
1
=GND/PE Earth Ground
4
1
3
2
Y
Disconnect and lockout/tag-
out input power before instal-
ling receptacle.
Y
Have only qualified persons
make this installation. See
rating label in Section 4-4, and
be sure to supply correct in-
put power.
1
Proper Receptacle
(NEMA 6-50R)
(User-Supplied)
Receptacle must comply with appli-
cable codes.
2
Input And Grounding
Conductors
See size and length using Section
4-7. Conductors must comply with
applicable codes.
3
Over-Current Protection
Select type and size of over-current
protection using Section 4-7.
4
Plug (NEMA 6-50P)
Connect plug to properly installed
receptacle.
Close and secure door on discon-
nect device. Remove lockout/tagout
device, and place switch in the On
position.
Содержание STICKMATE LX
Страница 4: ......
Страница 38: ...Notes ...