HBU Series Braking Unit
34
Chapter 6 Normal malfunction elimination
6.1 Exist braking sound and overvoltage in inverter.
Deceleration time of inverter is too short, postpone
deceleration time
Value of braking resistor is too big, re-calculate value
of resistor and select brake unit.
Not enough capacity for brake unit, re-check
specification of selected braking unit is right or not.
6.2 No braking sound
Wrong model selection for brake unit or working
voltage is unmatched.
Resistor
disconnected
or
cables
are
not
well-connected, brake is ineffective.
Resistor short out, brake stop output automatically.
Brake unit malfunctions.
6.3 Braking resistor too hot
Power for selected braking resistor is too low, increase
power of braking resistor.
6.4 Resistor keep heating when inverter stop working
Wrong model selection of brake unit or working
voltage is unmatched.
On-site network voltage fluctuates too much, beyond
operation voltage.
Wrong settings for operation voltage