3.4 wiring specification of major loop
Table 3.1 wiring specification of major loop
Models
Specifications
Rated
Current
Peak
Current
Section
of
Copper cable
HBU-1L
6A
33A
4 mm
2
HBU-1SA
10A
50A
4 mm
2
HBU-3SA
12A
100A
10 mm
2
HBU-3HA
70A
150A
16mm
2
HBU-4HA
85A
200A
16 mm
2
HBU-5HA
120A
300A
25 mm
2
HBU-5HA
160A
400A
32 mm
2
Soft cable is more flexible. Because of possible contact with
high-temperature device, please adopt copper core, heat-resistant and
anti-flaming cable.
Install braking unit close to inverter as possible as you can, no
more than 1 meter. Otherwise, please twist cables of direct current side
to reduce radiation and inductance.