Set-up process and troubleshooting
Pre-requisites
It is necessary to have a BACnet IP client or MSTP device operative and well connected to the corresponding BACnet
port of Intesis and a Modbus RTU slave or Modbus TCP client connected to their corresponding ports as well.
Connectors, connection cables, PC to use the configuration tool and other auxiliary material, if needed, are not
supplied by HMS Industrial Networks S.L.U for this standard integration.
Items supplied by HMS Networks for this integration are:
•
Intesis gateway.
•
Link to download the configuration tool.
•
USB Console cable to communicate with Intesis.
•
Product documentation.
Intesis MAPS. Configuration & monitoring tool for Intesis BACnet series
7.2.1 Introduction
Intesis MAPS is a Windows
®
compatible software developed specifically to monitor and configure Intesis BACnet
series.
The installation procedure and main functions are explained in the
Intesis MAPS User Manual
. This document can
be downloaded from the link indicated in the installation sheet supplied with the Intesis device or in the product
website at
In this section, only the specific case of Modbus to BACnet systems will be covered.
Please check the Intesis MAPS user manual for specific information about the different parameters and how to
configure them.
7.2.2 Connection
To configure the Intesis connection parameters press on the
Connection
button in the
menu bar
.