BACnet Server
– Modbus Client
User Manual r1.10 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
19 / 41
5.2.5 Binary Input Object Type
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Binary Input, 0)
R
R
Object_Name
CharacterString
Configurable through Config Tool
R
R
Object_Type
BACnetObjectType
BINARY_INPUT (3)
R
R
Present_Value
BACnetBinaryPV
INACTIVE (0) / ACTIVE (1)
R
R
Description
CharacterString
Configurable through Config Tool
O
R
2
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Polarity
BACnetPolarity
NORMAL (0)
R
R
Inactive_Text
CharacterString
Configurable through Config Tool
O
R
Active_Text
CharacterString
Configurable through Config Tool
O
R
Time_Delay
Unsigned
-
O
R
1
Notification_Class
Unsigned
-
O
R
1
Alarm_Value
BACnetBinaryPV
-
O
R
1
Event_Enable
BACnetEventTransitionBits
-
O
R
1
Acked_Transitions
BACnetEventTransitionBits
-
O
R
1
Notify_Type
BACnetNotifyType
-
O
R
1
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R
1
Event_Detection_Enable
BOOLEAN
-
O
R
Property_List
BACnetARRAY[N] of
BACnetPropertyIdentifier
-
R
R
1
Only available when specific object has a Notification Class configured
2
Only available in some models after activations on the configuration tool, review the specific model manual for
details