Chapter 3
Configuration Interface (RS232)
This interface provides a simple text baseed user interface via the onboard RS232 interface. All network
configuration parameters are available using a standard terminal emulator such as the Windows Hyper-
terminal.
Note that data exchange is halted and no mailbox activity is possible while using this interface.
The interface uses the following communication settings:
Terminal emulation: ASCII
Baudrate:
38400
Databits:
8
Stopbits:
1
Parity:
None
Flowcontrol:
None
Menu Tree Overview
Menu Level 1
Menu Level 2
Menu Level 3
Menu Level 4
(Main Menu)
View scan-lists
View all nodes
Select Node
Change Param
Parameter
Change NV Param
NV Parameter
Change NV I/O
NV I/O
Change NV ID
NV ID
Change NV Ext ID1
NV Ext ID1
Change NV Ext ID2
NV Ext ID2
Change Node address
Node address
View all detected nodes Select Node
Change Param
Parameter
Change NV Param
NV Parameter
Change NV I/O
NV I/O
Change NV ID
NV ID
Change NV Ext ID1
NV Ext ID1
Change NV Ext ID2
NV Ext ID2
Change Node address
Node address
View single node
Select Node
Change Param
Parameter
Change NV Param
NV Parameter
Change NV I/O
NV I/O
Change NV ID
NV ID
Change NV Ext ID1
NV Ext ID1
Change NV Ext ID2
NV Ext ID2
Change Node address
Node address
Toggle Mode
Select Configuration
Configuration Mode
Select Protected
Protected Mode
Toggle online/offline
Select online
Online
Select offline
Offline
Toggle auto address
enabled / disabled
Enable Auto Address
Enabled
Disable Auto Address
Disabled
Save Configuration
Configuration Saved