Fieldbus Specific Area 5-5
Node ID Code (address 71Ah - 759h)
Each byte in this area holds the ID Code of a specific slave.
Due to the nature of the extended addressing scheme used in AS-Interface v2.1, node number 32 has
no ID code.
Node Parameter (address 75Ah - 799h)
Each byte in this area holds the permanent parameter for a specific slave. Consult the AS-Interface spec-
ification for more information about node parameters.
Due to the nature of the extended addressing scheme used in AS-Interface v2.1, node number 32 con-
tains no parameters.
Config Mode (address 79Ah)
This byte indicates if the Configuration Interface is activate.
• 0h
Not Active
• 1h
Active
Running / Idle Mode (address 79Bh)
This byte indicates if the module is in running or idle mode.
• 0h
Module running, data exchange possible
• 1h
Module idle, no data exchange possible
Byte / Nibble Mode (address 79Ch)
This byte indicates if I/O data is represented in byte or nibble mode.
• 0h
Byte Mode
• 1h
Nibble Mode