![HMS AnyBus-M Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/hms/anybus-m/anybus-m_manual_2141663010.webp)
About the AnyBus-M AS-Interface 1-3
Indicators
AS-Interface Watchdog
• Flashing
The AS-Interface is working properly.
• Off
Module not initialised or AS-Interface network not working properly.
AnyBus Watchdog
Consult the general AnyBus-M Design Guide for further information.
Status Indicators
These leds indicate run time status and errors to the user.
Note:
If the module receives the mailbox command SW_RESET (i.e a soft reset) all 4 leds will flash red
4 times.
Led
State
Description
1 - Running / Idle
Green
Module is in running mode
Red
Module is in idle mode
2 - Network Status
Off
No power or not initialised
Flashing Green On line according to configuration
Green
On line, but no connections established
Red
Offline
3 - Module Status
Off
No power or not initialised
Flashing Green Protected mode
Green
Configuration mode
Red
Power Fail bus
4 -Auto prog, slave 0 exist
Off
No error, no slave 0, autoprogramming not possible
8Hz Green
Auto programming possible
1Hz Green
Slave address 0 exist
Red
Periphery error
8Hz Red
Periphery error, auto-programming possible
1Hz Red
Periphery error, slave with address 0 exist
1
2
4
3