Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply. Respect polarity applied of
terminals (+) and (-). Be sure the voltage applied is within the range admitted (check section 10). The power supply
can be connected to earth but only through the negative terminal, never through the positive terminal.
Ethernet / BACnet IP (UDP) / Modbus TCP / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5 cable.
If communicating through the LAN of the building, contact the network administrator and make sure traffic on the port
used is allowed through all the LAN path (check the gateway user manual for more information). With factory settings,
after powering up the gateway, DHCP will be enabled for 30 seconds. After that time, if no IP is provided by a DHCP
server, the default IP 192.168.100.246 will be set.
PortA / BACnet MS/TP
Connect the EIA485 bus to connectors A3 (A-), A4 (B+
) and A1 or A2 (SNGD) of gateway’s PortA. Respect the
polarity. Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum
32 devices connected
to the bus, and in each end of the bus it must be a termination resistor of 120 Ω. The gateway
has an internal bus biasing circuit that incorporates the termination resistor. If you install the gateway in one of the
ends of the bus, then do not install an additional termination resistor in that end.
PortB
Reserved for future use.
PROFINET
Connect the cables coming from the IP network to the PROFINET connectors.
Console Port