from the back– min. 500mm;
from above – min. 700mm.
For reference position of Smart Fire boiler inside boiler room that meets above requirements consult
Figure No. 20.
In case of SF11/130L boiler, the following requirements apply:
In front of boiler – min. 1000mm;
on side of boiler from side of flue chimney breeching– min. 500mm;
from side– min. 800mm;
from back– min. 500mm;
from above– min. 600mm.
In case of SF COMPACT boiler the following requirements apply:
In front of boiler – min. 1000 mm;
on side of boiler from side of flue chimney breeching – min. 600mm;
from side – min. 500mm;
from back – min. 500mm;
from above – min. 500mm.
Boiler room must be provided with appropriate supply-exhaust ventilation, with supply duct
running under the floor of boiler room, and exhaust duct running under the structural floor. Boiler
room must be provided with fire-rated door EI30. Door shall be fitted with self-closer. Boiler room
door shall be closed during boiler operation.
Figure No. 20 Reference position of Smart Fire SF41 boiler with 400L dispenser in boiler room.
9.3 Flue chimney
Due to required low chimney draft, exhaust gas low temperature and possible condensate
always check carefully regarding flue liner!
Clay flue liner is recommended or heat-resistant stainless that ensure proper conditions for
boiler operation!