background image

Copyright HK Instruments 2019

www.hkinstruments.fi

Installation version 8.0 2019

The seller is obligated to provide a warranty of five years for the deliv-
ered goods regarding material and manufacturing. The warranty period 
is considered to start on the delivery date of the product. If a defect in 
raw materials or a production flaw is found, the seller is obligated, when 
the product is sent to the seller without delay or before expiration of 
the warranty, to amend the mistake at his/her discretion either by re-
pairing the defective product or by delivering free of charge to the buy-
er a new flawless product and sending it to the buyer. Delivery costs 
for the repair under warranty will be paid by the buyer and the return 
costs by the seller. The warranty does not comprise damages caused by 
accident, lightning, flood or other natural phenomenon, normal wear 
and tear, improper or careless handling, abnormal use, overloading, im-
proper storage, incorrect care or reconstruction, or changes and instal-
lation work not done by the seller or his/her authorized representative. 
The selection of materials for devices prone to corrosion is the buyer’s 
responsibility, unless otherwise is legally agreed upon. Should the man-
ufacturer alter the structure of the device, the seller is not obligated to 
make comparable changes to devices already purchased. Appealing for 
warranty requires that the buyer has correctly fulfilled his/her duties 
arisen from the delivery and stated in the contract. The seller will give 
a new warranty for goods that have been replaced or repaired within 
the warranty, however only to the expiration of the original product’s 
warranty time. The warranty includes the repair of a defective part or 
device, or if needed, a new part or device, but not installation or ex-
change costs. Under no circumstance is the seller liable for damages 
compensation for indirect damage.

Register

Parameter description

Data Type

Value

Range

3x0001

Program version

16 bit

0...1000

0,00...99,00

3x0002

Pressure reading

16 bit

-250...2500/7000

-250...2500/7000 (Pa)

3x0004

Input 1: 0...10 V

16 bit

0...1000

0...100 %

3x0005

Input 1: Pt1000

16 bit

-500...500

-50...+50 °C

3x0006

Input 1: Ni1000

16 bit

-500...500

-50...+50 °C

3x0007

Input 1: Ni1000-LG

16 bit

-500...500

-50...+50 °C

3x0008

Input 1: NTC10k

16 bit

-500...500

-50...+50 °C

3x0009

Input 2: 0...10 V

16 bit

0...1000

0...100 %

3x0010

Input 2: Pt1000

16 bit

-500...500

-50...+50 °C

3x0011

Input 2: Ni1000

16 bit

-500...500

-50...+50 °C

3x0012

Input 2: Ni1000-LG

16 bit

-500...500

-50...+50 °C

3x0013

Input 2: NTC10k

16 bit

-500...500

-50...+50 °C

Function 04 - Read input register

Function code 02 - Read input status

Register

Parameter description

Data Type

Value

Range

1x0001

Input 1: BIN IN

Bit 0

0...1

On - Off

1x0002

Input 2: BIN IN

Bit 0

0...1

On - Off

Function 05 - Write single coil

Register

Parameter description

Data Type

Value

Range

0x0001

Zeroing function

Bit 0

0...1

On - Off

Function code 06 - Write single register

Register

Parameter description

Data Type

Value

Range

4x0001

Beta value of NTC thermistor

16 bit

0...30000

1...30000 (Default: 4220)

STEP 6: MODBUS REGISTERS

WARRANTY POLICY

RECYCLING/DISPOSAL

The  parts  left  over  from  installation  should  be 
recycled  according  to  your  local  instructions. 
Decommissioned  devices  should  be  taken  to  a 
recycling site that specializes in electronic waste.

Содержание DPT-IO-MOD Series

Страница 1: ...asurement points DPT IO MOD series devices are commonly used in HVAC R systems for fan blower and filter monitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy from applied pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Including general ac...

Страница 2: ...y for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Figure 1b Mounting orientation Figure 1c Application connections DPT DPT Display connection A B 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal block...

Страница 3: ...er 3x0008 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 5 Select the pressure unit for display Pa inchWC mmWC psi mbar PRESS UNIT Pa SELECT UP DOWN 6 Select the response...

Страница 4: ...y for goods that have been replaced or repaired within the warranty however only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or ex change costs Under no circumstance is the seller liable for damages compensation for indirect damage Register Parameter description Data ...