COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS
WPHBA / WPHA
OPTIONAL
VENTILADORES CON MOTOR EC
Cleaning
Danger due to electric current
Clean the circulation area of the air fan.
Attention!
Do not use any aggressive, paint solvent cleaning agents when cleaning.
Make sure that no water gets inside the motor and the electronics (e.g. by direct contact with seals of motor openings),
observe protection class (IP).
It is necessary to check the free flow of the condensation water evacuation openings (if there are any) that are
appropriate for set up position.
In case of improper cleaning work no guarantee is assumed regarding corrosion formation / paint adhesion for
unpainted / painted fans.
To avoid humidity accumulation in the motor, the fan must be operated at least for 1 hour at 80 to 100% of maximum
speed before cleaning!
After the cleaning process, the fan must be operated for 2 hours at 80 to 100% of maximum speed for drying purposes!
Voltage supply for motor must be interrupted and secured against restoration!