COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS
WPHBA / WPHA
OPERATION
Description of the Alarm Codes
CODE
DESCRIPTION
AL01
Alarm probe B1 disconnected (Outdoor temperature)
AL02
Alarm probe B2 disconnected (Supply temperature)
AL03
Alarm probe B3 disconnected (Discharge temperature comp.1)
AL05
Alarm probe B5 disconnected (Return temperature)
AL06
Alarm probe B6 disconnected (Return temperature)
AL07
Alarm probe B7 disconnected (Outdoor humidity)
AL08
Alarm probe B8 disconnected (Inlet water temperature circuit 2)
AL09
Alarm probe B9 disconnected (Outlet water temperature circuit 3)
AL11
Alarm probe B11 disconnected (Low pressure C1, only units w/2 circuits)
AL12
Alarm probe B12 disconnected ( Low pressure C2, only units w/2 circuits )
ALb1
Alarm probe B1 disconnected (Outdoor temperature)
ALb2
Alarm probe B2 disconnected (Supply temperature)
ALb3
Alarm probe B3 disconnected ( Discharge temperature comp.1)
ALb5
Alarm probe B5 disconnected (Return temperature)
ALb6
Alarm probe B6 disconnected (Return temperature)
ALb7
Alarm probe B7 disconnected (Outdoor humidity)
ALb8
Alarm probe B8 disconnected ( Inlet water temperature circuit 2)
ALb9
Alarm probe B9 disconnected ( Outlet water temperature circuit 3)
ALF6
Thermal alarm compressor
ALF7
Thermal alarm indoor fan
ALH1
Antifrost alarm 1 (Inlet water below 12ºC)
ALH2
Antifrost alarm 2 (Outlet water below 6ºC)
ALH3
Antifrost alarm 3 (Inlet water < 15ºC y
ΔT > 8ºC)
ALH4
Antifrost alarm 4 (Compressor ON y
ΔT Inlet/Outlet water lower than 1.5ºC)
ALIF
Alarm flow switch
ALPA
Alarm high pressure switch circuit 1
ALPB
Alarm low pressure switch circuit 1
ALPM
Alarm minimum pressure switch
ALRF
Alarm missing refrigerant
A2F7
Thermal alarm compressor 2 (machine 2 circuits)
A2F8
Thermal alarm indoor fan 2 (machine 2 circuits)
A2PA
Alarm high pressure switch circuit 2
A2PB
Alarm low pressure switch circuit 2
A2PM
Alarm minimum pressure switch circuit 2
A2RF
Alarm falta de refrigerante circuito 2