COMPACT HORIZONTAL PACKAGED WATER-TO-AIR UNITS
WPHBA / WPHA
OPERATION
OPERATING LIMITS
Cooling cycle
INPUT TEMPERATURE
MINIMUM
MAXI MUM
Dry indoor air
19ºC
31ºC
Wet indoor air
15ºC
21ºC
Water inlet
15ºC *
45ºC **
*For water inlets lower than 25ºC, it is necessary to install the presostatic valve accessory.
** On request units can be manufactured to 50 ºC.
Heating cycle
INDOOR FAN TRANSMISSION ADJUSTMENT
Adjust transmission in such a way that the indoor motor consumption comes to its nominal value.
If consumption is below nominal value it means that unit air flow is too low.
To change fan speed
:
1. Remove the belt. Move the motor along its track (or loosen the tensor set screw) in order to release it.
2. Loose the set screws of the motor pulley and turn the movable flange. Open or close depending on the needs
(Open: speed decreases).
3. Tighten set screws.
4. Place the belt in the pulley channel. The closure or opening of the pulley could void the size of the prior belt. In
this case, replace it for other belt of the same profile and with the appropriate length.
5. Tighten the belt by using tensor screw or sliding the motor, depending on the case.
TEMPERATURE
MINIMUM
MAXI MUM
Dry air inlet
18ºC
24ºC
Water inlet
12ºC
27ºC
1.
Motor
2.
Motor pulley
3.
Transmission belt
4.
Fan pulley
5.
Tensor set screw
6.
Set screw
7.
Fixed flange
8.
Movable flange