SECTION II: INSTALLATION AND MAINTENANCE 

 

 

 

o

  The following is memorised for each alarm: 

  date and time of intervention (if the KSC accessory is present); 

  in/out water temperature values as soon as the alarm is triggered; 

  the condensation pressure values at the time of the alarm 

  alarm delay from when the connected device is switched on; 

  compressor status at the time of the alarm; 

o

  Advanced functions: 

  Hi-Pressure Prevent function with forced cooling capacity 

partialisation for a high outdoor temperature (in summer mode), 

  set-up for serial connection (KRS485, KFTT10, KRS232, KUSB 

accessory); 

  possibility to have a digital input for remote management of the 

double Set point (see the Pre-sales Department); 

  possibility to have an analogue input for the shifting Set-point via a 

4-20mA remote signal (contact Pre-sales Department); 

  set-up for management of time bands and operating parameters with 

the possibility of daily/weekly operating programs (KSC accessory); 

  check-up and verification of the scheduled maintenance status; 

  computer-assisted machine testing; 

  self-diagnosis with continuous monitoring of the machine operating 

status. 

II.2 

ACCESSORIES 

II.2.1 

Factory fitted accessories 

P1 

– Installation with pump. 

P2 

– Installation with increased head pump. 

DP1 

– Installation with double pump, one of which in standby with 

automatic activation. 

DP2 

– Installation with increased head double pump, one of which in 

standby with automatic activation. 

ASP1 

– Installation with pump and storage tank. 

ASP2 

– Installation with increased head pump and storage tank. 

ASDP1 

– Installation with double pump, one of which in standby with 

automatic activation and storage tank. 

ASDP2 

– Installation with increased head double pump, one of which in 

standby with automatic activation and storage tank. 

INS

– Soundproofed compressors with noise-absorbing ear muff 

(solution that reduced the noise of the compressors). 

RA 

– Evaporator anti-freeze resistance, prevents the risk of ice 

formation inside the exchanger when the machine is switched off 
(provided the unit remains powered). 

RDR 

– Desuperheater/recovery unit anti-freeze resistance (DS or 

RC100), prevents the risk of ice formation inside the recovery unit 
exchanger when the machine is switched off (provided the unit remains 
powered). 

RAS 

– 300W storage tank anti-freeze resistance (available for ASP1- 

ASDP1- ASP2-ASDP2 set-ups); prevents the risk of ice formation inside 
the exchanger tank when the machine is switched off (provided the unit 
remains powered). 

RAE 1 

– 27W electric pump anti-freeze resistance (available for P1- 

DP1-ASP1-ASDP1 set-ups); prevents the risk of the water inside the 
pump becoming ice when the machine is switched off (provided the unit 
remains powered). 

RAE 2 

– 27W double electric pump anti-freeze resistance (available for 

P2-DP2-ASP2-ASDP2 set-ups); prevents the risk of the water inside the 
pumps becoming ice when the machine is switched off (provided the 
unit remains powered). 

DS 

– Desuperheater; it is not active during heat pump operation. 

RC100 

– Heat recovery unit with 100% recovery; the accessory is 

complete with a differential pressure switch on the recovery unit 
exchanger. It does not work as a heat pump. 

GM 

– Cooling circuit high and low pressure gauges. 

SFS 

– Soft-Start device to reduce the peak current in the start-up phase 

(weight 40 Kg). 

FTT10 

– FTT10 serial interface board for connection to supervision 

systems (LonWorks

® 

system compliant with Lonmark

® 

8090-10 protocol 

with chiller profile). 

SS 

– RS485 serial interface board to create dialogue networks between 

boards (maximum: 200 units for a max. distance of 1000 m) and the 
building automation or external supervision systems. 

CR 

– Power factor correction capacitors (cosΦ > 0.91). 

EEV 

– Electronic thermostatic valve. 

RAP 

– Unit with copper/pre-painted aluminium coils. 

BRR 

– Unit with copper/copper coils. 

DSP 

– Double Set-point via digital consensus (incompatible with the CS 

accessory). 

BT 

– low temperature of water produced (only for models 270÷2160). 

CS 

– 4-20 mA analogue signal for shifting Set-point (incompatible with 

the DSP accessory). The EEV accessory may have to be also installed, 
depending on the required values. 

RPB 

– Coil protection mesh with accident-prevention function. 

IMB 

– Protective packaging. 

II.2.2 

Accessories supplied separately 

KFA 

- Water filter (only for models 233÷265). 

KRAS 

- Fitting for connection to the inlet duct. 

KRMA 

- Antivibration fitting for connection to the outlet duct. 

KSA 

– Rubber antivibration mountings. 

KRIT 

– Additional electrical resistance heater for heat pump only for 

233÷265. 

KEAP 

– Outdoor air temperature probe for Set-point compensation 

(incompatible with the CS accessory). 

KTR 

– Remote control keyboard with backlit LCD display (same 

functions as that on the machine). 

KSC 

– Clock card to display the date/time and machine time band 

management with daily and weekly start/stop time bands, with the 
possibility of changing the Set-points. 

KRS485 

– RS485 serial interface board to create dialogue networks 

between boards (maximum: 200 units for a max. distance of 1000 m) 
and the building automation or external supervision systems. 

KFTT10 

– FTT10 serial interface board for connection to supervision 

systems (LonWorks

® 

system compliant with Lonmark

® 

8090-10 protocol 

with chiller profile). 

KISI 

– CAN bus serial interface (Controller Area Network). 

KRS232 

– RS485/RS232 serial converter for interconnection between 

the RS485 serial network and supervision systems with serial 
connection to the PC via the RS232 serial port (RS232 cable supplied). 

KUSB 

– RS485/USB serial converter for interconnection between the 

RS485 serial network and supervision systems with serial connection to 
the PC via the USB port (USB cable supplied). 

KMDM 

– GSM 900-1800 modem kit to be connected to the unit for 

remote management of the parameters and any alarm signals. The kit 
consists of a GSM modem with relative RS232 board. A SIM data card, 
not supplied must be purchased. 

KRS 

– Supervision software for the monitoring and remote 

management of the units. The kit consists of a CD-Rom and hardware 
key. 

Содержание EQU-PF 2100

Страница 1: ...eversibles monobloque de alto rendimientoconcondensaci nporaireyventiladorescentr fugos tipoPlug Fan conmotoresEC Air cooled chillers and heat pumps with radial fans Modelos 233 238 245 250 260 265 27...

Страница 2: ...s to prevent hazard zones being reached by upper and lower limbs UNI EN 563 Safety of machinery Temperature of contact surfaces Ergonomic data to establish limit values for temperatures of hot surface...

Страница 3: ...ce connection I 2 MACHINE IDENTIFICATION The identification data is found on the serial number plate which is located near the electrical panel The serial number plate must not be removed for any reas...

Страница 4: ...r inlet temperature 47 C If the water inlet temperature to the condensers is lower than the permitted values it is recommended to use a three way modulating valve toguarantee EQU PF EQUH PF 270 2160 M...

Страница 5: ...ned guidelines can cause personal injury or damage the unit Avoid inhalation of high concentrations of vapour The atmospheric concentration must be minimised and maintained at this minimum level below...

Страница 6: ...al power supply Indicates the presence of live components Indicates the presence of moving parts belts fans Indicates the presence of hot surfaces refrigeration circuit compressor heads Indicates the...

Страница 7: ...In the case of a single pump the unit is also complete with a delivery shut off valve In the case of a double pump the unit is complete with a non return valve and an intake valve for each pump Tank P...

Страница 8: ...ed the unit remains powered DS Desuperheater it is not active during heat pump operation RC100 Heat recovery unit with 100 recovery the accessory is complete with a differential pressure switch on the...

Страница 9: ...tional or local regulations in force at the time of installation Some internal parts of the unit can cause cuts Use suitable individual protective equipment If the unit is not secured on the antivibra...

Страница 10: ...nit bear the following in mind non soundproofed reflecting walls near the unit can increase the total sound pressure level read near the appliance by 3 dB A for every surface install suitable antivibr...

Страница 11: ...The screening must be connected to the earth screw on the panel on one side only The maximum permitted distance is 30 m CS Shifting Set point 4 20 mA signal SDS Double Set point selector control with...

Страница 12: ...t be installed as well as system machine drain taps The rate of the water that flows through the heat exchanger must not drop below the value corresponding to a temperature differential of 8 C with bo...

Страница 13: ...lect the TANK PUMP accessory complete with inertial storage tank and possibly install an additional tank However in process applications it is always advisable to use a storage tank or a greater syste...

Страница 14: ...mation regarding performance of the units From 3 C to 8 C 30 From 0 C to 2 C 20 From 4 C to 1 C 10 Table H Minimum outdoor air temperature C 2 0 3 6 10 15 20 glycol in weight 10 15 20 25 30 35 40 Free...

Страница 15: ...p PD RC100 DS consensus differential pressure switch FC Fan coil UT Upon use RI From the water mains ST Temperature probe SI Intermediate exchanger ST8 RC100 DS outlet temperature probe VSAC Water saf...

Страница 16: ...he terminals of the power supply and of the contactors are tightened they may loosen during transport which could lead to malfunctions IMPORTANT The electrical connections must be made in compliance w...

Страница 17: ...tion direction Do the pumps turn the right way Restore the water flow rate Is the water flow rate compliant with that indicated in the user manual Fill the circuits and or bleed the air Are the circui...

Страница 18: ...el ON OFF key All ON OFF operations must be carried out EXCLUSIVELY using the ON OFF key on the control panel NO Does the earthing conform to current regulations Are the power circuit electric conduct...

Страница 19: ...s anomaly If you take the pressure on the high pressure side to approx 8 bar are there gas leaks 3 grams year Stop the unit and verify the cause of the leak according to EN 378 2 Do alarms appear on t...

Страница 20: ...probe from the socket taking care not to damage it in the process The probe must be carefully repositioned by placing some conductive paste in the socket inserting the probe and re sealing the extern...

Страница 21: ...orrosion on the unit framework Any corrosion detected must be treated with protective paints in order to prevent possible damage II 9 1 2 Cleaning finned coils DANGER Pay attention to the edges of the...

Страница 22: ...f necessary start up the utility pump 1 EQU PF EQUH PF 2 Auxiliary cock 3 Shut off gate valve 4 Wash pump 5 Filter 6 Acid tank II 9 2 Special Maintenance These are all those repairs or replacements th...

Страница 23: ...nlet pipe If during the test phase the shut off valve closes completely without tripping the differential pressure switch switch off the unit immediately by pressing the ON OFF key on the control pane...

Страница 24: ...unctions Insufficient cooling air to the coils check fans check clearances around unit and possible coil obstructions High ambient temperature check unit operation limits Refrigerant charge excessive...

Страница 25: ...ystem size leaks and insulation Irregular operation of the expansion valve verify functions and replace if necessary Mechanical problems in the compressor repair compressor Insufficient refrigerant to...

Страница 26: ...or y al personal encargado del mantenimiento sobre los riesgos debidos a la presencia de tensi n PELIGRO DE SUPERFICIES CORTANTES La indicaci n de PELIGRO DE SUPERFICIES CORTANTES se utiliza para info...

Страница 27: ...ICACI N DE LA M QUINA Los datos de identificaci n se encuentran en la placa de caracter sticas aplicada cerca del cuadro el ctrico Esta placa no debe retirarse bajo ninguna circunstancia en caso de de...

Страница 28: ...trada 47 C Si la temperatura del agua en la entrada de los condensadores es inferior a los valores admitidos se recomienda el uso de una v lvula de tres v as Modelos EQU PF EQUH PF 270 2160 En inviern...

Страница 29: ...deben reducirse y mantenerse al nivel m nimo por debajo del l mite de exposici n profesional Los vapores son m s pesados que el aire por lo que es posible que se verifiquen concentraciones elevadas en...

Страница 30: ...bajo tensi n Se ala la presencia de rganos en movimiento correas ventiladores Se ala la presencia de superficies calientes circuito frigor fico cabezas de los compresores Se ala la presencia de arist...

Страница 31: ...n Si se cuenta con bomba doble la unidad dispone de una v lvula de no retorno y de una v lvula en la aspiraci n para cada bomba Tank Pump ASP1 Montaje con bomba y acumulador ASP2 Montaje con bomba co...

Страница 32: ...se apaga la m quina siempre y cuando la unidad siga recibiendo energ a el ctrica DS Desobrecalentador no est activo en el funcionamiento como bomba de calor RC100 Recuperador de calor con recuperaci...

Страница 33: ...rendimiento PELIGRO Es responsabilidad del personal respetar las normativas locales y nacionales vigentes al poner la m quina en funcionamiento Algunas partes internas de la unidad podr an causar cor...

Страница 34: ...KRAS Racor antivibratorio de aspiraci n KRAM Racor antivibratorio de impulsi n Al instalar la unidad tenga en cuenta los siguientes puntos Las paredes reflectantes no aisladas ac sticamente cerca de...

Страница 35: ...5 mm y el blindaje El blindaje se debe conectar a la barra de tierra presente en el cuadro en un solo lado La distancia m xima prevista es de 30 m CS Punto de consigna variable se al 4 20 mA SDS Sele...

Страница 36: ...de la instalaci n y juntas el sticas de uni n al igual que grifos de desag e instalaci n m quina El caudal de agua a trav s del intercambiador no debe bajar a un valor inferior a un salto t rmico de...

Страница 37: ...indicado o calculado es oportuno elegir el accesorio TANK PUMP con dep sito acumulador inercial y de ser posible instalar un dep sito adicional Aun as en las aplicaciones de proceso siempre es aconse...

Страница 38: ...ener informaci n sobre las prestaciones de las unidades de 3 C a 8 C 30 de 0 C a 2 C 20 de 4 C a 1 C 10 Tabla H Temperatura m nima del aire exterior C 2 0 3 6 10 15 20 glicol en peso 10 15 20 25 30 35...

Страница 39: ...de circulaci n PD Presostato diferencial permiso RC100 DS FC Fan coil UT En el uso RI De la red hidr ulica ST Sonda de temperatura SI Intercambiador intermedio ST8 Sonda temperatura de salida RC100 D...

Страница 40: ...cuadro el ctrico y compruebe que los bornes de la alimentaci n y de los contactores est n apretados durante el transporte se pueden aflojar y esto puede causar problemas de funcionamiento IMPORTANTE...

Страница 41: ...filtros de agua puestos antes del evaporador y del recuperador si est presente funcionan y est n correctamente instalados Restablezca o sustituya el componente Los interruptores de caudal instalados...

Страница 42: ...EXCLUSIVAMENTE mediante el bot n ON OFF que se encuentra en el panel de mandos NO La conexi n de tierra cumple con las disposiciones de ley Los conductores el ctricos del circuito de potencia tienen l...

Страница 43: ...a causa de la alarma V ase la tabla de las alarmas Hay alarmas en el display de la unidad Detenga la unidad y busque la causa de la fuga seg n EN 378 2 Si se pone la presi n en el lado de alta presi n...

Страница 44: ...n colocadas dentro de un pozo en contacto con una pasta conductiva y bloqueadas en la parte externa con silicona Una se encuentra en la entrada del intercambiador y mide la temperatura del agua de ret...

Страница 45: ...si n que puedan producirse deben tratarse con pinturas protectoras para evitar posibles da os II 9 1 2 Limpieza de las bater as de aletas PELIGRO Preste atenci n a los bordes afilados de la bater a Pa...

Страница 46: ...iento la bomba de la aplicaci n 1 EQU PF EQUH PF 2 Grifo auxiliar 3 V lvula de corte de compuerta 4 Bomba de lavado 5 Filtro 6 Dep sito del cido II 9 2 Mantenimiento extraordinario Es el conjunto de i...

Страница 47: ...ta por el usuario en el conducto de entrada de agua a la unidad Si durante la fase de prueba se llega a cerrar completamente la v lvula de corte sin la intervenci n del presostato diferencial apague i...

Страница 48: ...amiento Aire de enfriamiento hacia las bater as insuficiente Revise que los ventiladores funcionen bien que se hayan dejado libres los espacios necesarios y que las bater as no presenten obstrucciones...

Страница 49: ...ciones y aislamiento La v lvula de expansi n no funciona correctamente Compruebe su funcionamiento y de ser necesario sustit yala Problemas mec nicos en el compresor Controle el compresor Carga de ref...

Страница 50: ...0 265 Absorbed power kW 13 8 13 2 17 9 22 4 25 0 26 9 Pump absorbed power P1 ASP1 P2 ASP2 kW 0 70 1 5 0 70 1 5 0 70 1 5 0 70 1 5 0 70 1 5 0 70 1 5 Electrical power supply V ph Hz 400 3 N 50 Auxiliary...

Страница 51: ...pressor plate Electrical data 270 280 290 2100 2115 2130 2145 2160 Absorbed power kW 27 0 29 7 33 8 40 5 42 7 47 0 54 2 60 4 Pump absorbed power P1 ASP1 P2 ASP2 kW 1 1 2 2 1 1 2 2 1 5 3 0 1 5 3 0 1 5...

Страница 52: ...3 17 1 21 3 23 4 26 2 Pump absorbed power P1 ASP1 P2 ASP2 kW 0 7 1 5 0 7 1 5 0 7 1 5 0 7 1 5 0 7 1 5 0 7 1 5 Electrical power supply V ph Hz 400 3 N 50 Auxiliary power supply V ph Hz 230 1 N 50 Contr...

Страница 53: ...ode kW 27 2 29 6 35 5 40 5 42 3 47 1 54 6 61 1 Absorbed power in winter mode 26 9 28 1 32 7 38 8 41 6 45 7 53 7 59 4 Pump absorbed power P1 ASP1 P2 ASP2 kW 1 1 2 2 1 1 2 2 1 5 3 0 1 5 3 0 1 5 3 0 1 5...

Страница 54: ...absorbida kW 13 8 13 2 17 9 22 4 25 0 26 9 Potencia absorbida bomba P1 ASP1 P2 ASP2 kW 0 70 1 5 0 70 1 5 0 70 1 5 0 70 1 5 0 70 1 5 0 70 1 5 Alimentaci n el ctrica de potencia V ph Hz 400 3 N 50 Alim...

Страница 55: ...3x2 33 3x2 12 3x2 16 4x2 25 4x2 25 Caudal nominal ventiladores m h 26000 26000 27000 39000 39000 39000 52000 52000 Altura manom trica est tica til m xima de los Pa 250 250 250 250 250 250 250 250 Con...

Страница 56: ...26 2 Potencia absorbida bomba P1 ASP1 P2 ASP2 kW 0 7 1 5 0 7 1 5 0 7 1 5 0 7 1 5 0 7 1 5 0 7 1 5 Alimentaci n el ctrica de potencia V ph Hz 400 3 N 50 Alimentaci n el ctrica auxiliar V ph Hz 230 1 N...

Страница 57: ...5 5 40 5 42 3 47 1 54 6 61 1 Potencia absorbida en funcion invierno 26 9 28 1 32 7 38 8 41 6 45 7 53 7 59 4 Potencia absorbida bomba P1 ASP1 P2 ASP2 kW 1 1 2 2 1 1 2 2 1 5 3 0 1 5 3 0 1 5 3 0 1 5 3 0...

Страница 58: ...2650 2650 2650 2650 2650 2650 d mm 724 724 724 724 724 724 e mm 1100 1100 1100 1100 1100 1100 f mm 2200 2200 2200 2200 2200 2200 g mm 322 322 322 322 322 322 h mm 257 257 257 257 257 257 i mm 176 176...

Страница 59: ...3200 3200 3200 3200 4000 4000 4000 4000 g mm 300 300 300 300 300 300 300 300 h mm 205 205 205 205 205 205 205 205 i mm 256 256 256 256 256 256 256 256 l mm 530 530 530 530 400 400 400 400 m mm 1833 1...

Страница 60: ...NOTE...

Страница 61: ...S L Masia Torrents 2 Tel 34 938 934 912 Fax 34 938 939 615 08800 Vilanova i la Geltr Barcelona Spain www hitecsa com Reservado el derecho a efectuar modificaciones sin previo aviso Subject to modifica...

Отзывы: