CCHA/ECHA – CCHBA/ECHBA
Installation, operation and maintenance instructions
11
DRAINAGE
•
Indoor drainage (of condensate water) has a 3/4” MPT connection.
•
Condensate drain line diameter should be equal or larger than the unit connection depending
on pipe length and general building configuration.
•
Drainage line should have a minimum inclination of 2% for proper water evacuation.
•
When drainage line is exposed to temperatures below 0ºC, it is necessary to provide thermal
insulation or electrical heating wire to avoid water freezing and tube damages
•
It is advisable to install a trap with proper dimensions.
AIR DUCTS
-
Air duct dimensions will be determined according to the airflow and available static pressure.
-
Ducts must be designed by qualified technical people.
-
Use ducts made of non-inflammable materials in order to avoid any emission of gas in case of
fire. It is advisable to use metal plate duct with insulation.
-
Use flexible ducts to connect air ducts into the unit and thus avoid vibration and noise
transmission.