background image

 

CCHA/ECHA – CCHBA/ECHBA  
Installation, operation and maintenance instructions 

1

 

 

Installation, operation and maintenance instructions 

 
 

CCHA / ECHA – Cooling Only 

CCHBA / ECHBA – Heat Pump                                               

 

SPLIT HORIZONTAL UNITS 
AIR-AIR 
 

 

                                                              

 

 

 

 

 

 

 

 

 

Содержание CCHA

Страница 1: ...HA ECHA CCHBA ECHBA Installation operation and maintenance instructions 1 Installation operation and maintenance instructions CCHA ECHA Cooling Only CCHBA ECHBA Heat Pump SPLIT HORIZONTAL UNITS AIR AI...

Страница 2: ...allation operation and maintenance instructions 2 CONTENTS INTRODUCTION 3 SAFETY PRECAUTIONS 4 RECEPTION 5 LOCATION INSTALLATION 8 START UP 10 TECHNICAL DATA 14 DIMENSIONS 16 REFRIGERANT CHARGE 22 REG...

Страница 3: ...e etc are potentially hazardous and must be kept out of reach of children Recycle packing materials in accordance with local legislation The units must be used only for the purpose for which they are...

Страница 4: ...ation operation and maintenance instructions as well as the ones indicated in labels of the unit Do not forget to strictly follow any other safety codes Use safety glasses work gloves and any other sa...

Страница 5: ...ccordance with local power supply In case of any flaw or anomaly detected please contact HITECSA RIGGING Before moving the unit make sure that all panels are well fixed Raise and set down the equipmen...

Страница 6: ...um service area according to Fig 2 Choose a place free of dust or any other foreign material that could clog or damage the condenser coil The location should also be a place that cannot be flooded Con...

Страница 7: ...d maintenance instructions 7 WEIGHT DISTRIBUTION Kg UNIT SETTLEMENT Make sure that the unit is correctly levelled The bed frame should be strong and solid enough to support the weight of the machine V...

Страница 8: ...nted o Grilles air diffusers air ducts and flexible connections are in good condition o Electrical power source is in accordance with what is said in the nameplate o Fans rotate in the right direction...

Страница 9: ...or circuit breaker MCB curve D 4 Main power switch 5 Indoor fan motor supply 400 3 or 230 1 6 Electric heating wiring option 7 Electric heating supply option de 400 3 or 230 1 8 Remote control OPERAT...

Страница 10: ...17 17 17 Potencia total absorbida 3 kW 2 6 3 2 3 7 4 8 4 9 6 2 Corriente total absorbida 3 A 13 19 12 15 15 13 Potencia total absorbida 4 kW 3 4 4 3 4 8 5 8 6 5 8 5 Corriente total absorbida 4 A 15 19...

Страница 11: ...mperatures below 0 C it is necessary to provide thermal insulation or electrical heating wire to avoid water freezing and tube damages It is advisable to install a trap with proper dimensions AIR DUCT...

Страница 12: ...ley 5 Tensor adjustment screw 6 Setscrew 7 Mobile flap 8 Fix flap 7 6 8 3 1 5 4 2 Polea Pulley abiertas Fijo Variable Correa kW A CCHBA 751 X 1 5 3 6 150 E25 1A 75 100 E 24 1A A 45 0 CCHBA 801 X 1 5 3...

Страница 13: ...r crew COMPRESSOR LUBRICANT Compressors with R410a refrigerant use synthetic polyester oil each manufacturer using a specific oil for his product The system must not remain open to the atmosphere more...

Страница 14: ...tro tubos 3 8 3 8 3 8 3 8 3 8 3 8 VENTILADOR INTERIOR Tipo Modelo 9 7 DD 9 9 DD 10 10 DD 10 10 DD 10 10 DD 10 10 SS Potencia motor kW 0 120 0 250 0 250 0 373 0 373 0 550 Voltaje V 230 1 230 1 230 1 23...

Страница 15: ...3 8 3 8 VENTILADOR INTERIOR Tipo Modelo 12 9 SS 12 9 SS 12 9 SS 12 9 SS 12 12 SS 15 15 SS Potencia motor kW 0 735 0 735 0 735 0 735 1 500 2 200 Voltaje V 400 3 400 3 400 3 400 3 400 3 400 3 Corriente...

Страница 16: ...CCHA ECHA CCHBA ECHBA Installation operation and maintenance instructions 16 DIMENSIONS CCHA CCHBA 351 ECHA ECHBA 351...

Страница 17: ...CCHA ECHA CCHBA ECHBA Installation operation and maintenance instructions 17 CCHA CCHBA 371 401 501 ECHA ECHBA 371 401 501...

Страница 18: ...CCHA ECHA CCHBA ECHBA Installation operation and maintenance instructions 18 CCHA CCHBA 701 721 751 801 ECHA ECHBA 701 721 751 801...

Страница 19: ...ne Circulation speed of the refrigerant Refrigerant mass DISCHARGE LINE In heat pump operation the gas line works as discharge line WARNING When working with the machines in operation discharge line t...

Страница 20: ...oor unit L NEA DE GAS L NEA DE L QUIDO A B A UNIDAD INTERIOR B UNIDAD EXTERIOR L NEA DE GAS L NEA DE L QUIDO L NEA DE GAS L NEA DE L QUIDO L NEA DE L QUIDO A B A UNIDAD INTERIOR B UNIDAD EXTERIOR A B...

Страница 21: ...ll be insulated only when exposed to high temperatures solar radiation etc Horizontal segment of suction line 4 pitch towards the compressor In addition to refrigerant sometimes it s necessary to add...

Страница 22: ...e and quick evaporation refrigerant R410A cannot be kept in liquid phase inside charge cylinder because bubbles would form making reading difficult WARNING If it s necessary to make welding operations...

Страница 23: ...every 1 000 hours Fan and motors do not need additional lubrication Drainage system verify condition and good operation of the drainage tray Make sure that holes at the base of the unit are not block...

Страница 24: ...A Installation operation and maintenance instructions 24 www hitecsa com HIPLUS AIRE ACONDICIONADO S L Masia Torrents 2 08800 Vilanova i la Geltr Barcelona Espa a Tel 34 93 893 49 12 Fax 34 93 893 96...

Отзывы: