º
10
IOM_ACVBA-ACVA_351a2402_207958_180109_EN
ACVBA-ACVA
PACKAGED VERTICAL COMPACT UNITS
AIR-AIR
TECHNICAL SPECIFICATIONS
MODEL
1502
1602
2002
2302
2402
CAPACITIES
Cooling capacity
kW
43.4
50.2
63.1
73.6
78.5
Heat capacity
kW
44.2
51.9
65.5
81.9
81.9
EER Coefficient
2.5
2.5
2.4
2.6
2.3
COP Coefficient
2.7
2.9
2.9
3
2.8
Number of refrigerating circuits
2
2
2
2
2
REFRIGERANT
Type
R410A
GWP (1)
2088
Load (2)
2 x 7.1
2 x 6.6
2 x 8.0
2 x 10.3
2 x 9.0
COMPRESSOR
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Number
2
2
2
2
2
Oil type
POE
POE
POE
POE
POE
Oil volume
l
2 x 2.8
2 x 2.8
2 x 2.8
2 x 2.3
2 x 3.3
Type
FV68S
FV68S
FV68S
160SZ
160SZ
OUTDOOR CIRCUIT FAN
Type
Centrifugal, double aspiration
Nominal air flow
m3/h
15600
16000
22000
23000
23000
Available static pressure
Pa
110
110
123
142
142
Model
2x15/15 SS
2x15/15 SS
2x18/18 SS
2x18/18 SS
2x18/18 SS
Power
kW
2 x 1.5
2 x 1.5
2 x 2.2
2 x 3
2 x 3
Speed
r.p.m.
808
808
671
734
787
INDOOR CIRCUIT FAN
Type
Centrifugal, double aspiration
Nominal air flow
m3/h
10000
10000
11000
12000
12000
Available static pressure
Pa
145
145
175
160
160
Model
12/12 G2L
12/12 G2L
15/11 G2L
15/11 G2L
15/11 G2L
Power
kW
2.2
2.2
3
3
3
Speed
r.p.m.
913
913
734
787
734
DIMENSIONS AND WEIGHT
Length
mm
2000
2000
2600
2600
2600
Width
mm
939
939
980
980
980
Height
mm
1997
1997
2174
2174
2174
Weight
kg
810
820
1080
1115
1135
1.
GWP: Global Warming Potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2, calculated in terms of 100-year
warming potential.
2.
Only units with “FLARE” valve as standard (not option) are loaded with refrigerant, the rest of them are loaded with dry nitrogen