57
“b” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data Units
b096
BRD activation level
Range is:
330 to 380V (200V class)
U
360 V
b097
BRD resistor value
Min.Resistance to 600.0
U
Min.
Resistance
Ohm
B100
Free V/F setting, freq.1
Set range, 0 ~ value of
b102
U
0. Hz
b101
Free V/F setting, voltage.1
Set range, 0 ~ 800V
U
0.0 V
b102
Free V/F setting, freq.2
Set range, value of
b100
~
b104
U
0. Hz
b103
Free V/F setting, voltage.2
Set range, 0 ~ 800V
U
0.0 V
b104
Free V/F setting, freq.3
Set range, value of
b102
~
b106
U
0. Hz
b105
Free V/F setting, voltage.3
Set range, 0 ~ 800V
U
0.0 V
b106
Free V/F setting, freq.4
Set range, value of
b104
~
b108
U
0. Hz
b107
Free V/F setting, voltage.4
Set range, 0 ~ 800V
U
0.0 V
b108
Free V/F setting, freq.5
Set range, value of
b108
~
b110
U
0. Hz
b109
Free V/F setting, voltage.5
Set range, 0 ~ 800V
U
0.0 V
b110
Free V/F setting, freq.6
Set range, value of
b108
~
b112
U
0. Hz
b111
Free V/F setting, voltage.6
Set range, 0 ~ 800V
U
0.0 V
b112
Free V/F setting, freq.7
Set range,
b110
~ 400
U
0. Hz
b113
Free V/F setting, voltage.7
Set range, 0 ~ 800V
U
0.0 V
B120
Brake control enable
Two option codes:
00
…
Disable
01
…
Enable
U
00
−
b121
Brake Wait Time for Release
Set range: 0.00 to 5.00 sec
U
0.00 sec.
b122
Brake Wait Time for
Acceleration
Set range: 0.00 to 5.00 sec
U
0.00 sec.
b123
Brake Wait Time for Stopping
Set range: 0.00 to 5.00 sec
U
0.00 sec.
b124
Brake Wait Time for
Confirmation
Set range: 0.00 to 5.00 sec
U
0.00 sec.
b125
Brake release freq.
Set range: 0 to 400Hz
U
0.00 sec.
b126
Brake release current
Set range: 0~200% of inverter rated
current
U
(rated
current)
A
b127
Braking freq. setting
Set range: 0 to 400Hz
U
0.00 Hz
B130
Deceleration overvoltage
suppression enable
00
…
Disabled
01
…
Enabled
02
…
Enabled with accel.
U
00
−
B131
Decel. overvolt. suppress level
DC bus voltage of suppression.
Range is:
200V class
…
330 to 395
U
380 V
b132
Decel. overvolt. Suppress
const.
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 sec.
U
1.00 sec.
B133
Decel. overvolt. Suppress
proportional gain
Proportional gain when b130=01.
Range is: 0.00 to 5.00
9
0.20
−