49
“A” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data
Units
a131
Acceleration curve constant
Range is 01 to 10.
U
02
−
a132
Deceleration curve constant
Range is 01 to 10.
U
02
−
A141
A input select for calculate
function
Seven options:
00
…
Operator
01
…
VR
02
…
Terminal [O] input
03
…
Terminal [OI] input
04
…
RS485
05
…
Option
07
…
Pulse train input
U
02
−
A142
B input select for calculate
function
Seven options:
00
…
Operator
01
…
VR
02
…
Terminal [O] input
03
…
Terminal [OI] input
04
…
RS485
05
…
Option
07
…
Pulse train input
U
03
−
A143
Calculation symbol
Calculates a value based on the
A input source (
A141
selects) and
B input source (
A142
selects).
Three options:
00
…
ADD (A input + B input)
01
…
SUB (A input - B input)
02
…
MUL (A input * B input)
U
00
−
A145
ADD frequency
An offset value that is applied to
the output frequency when the
[ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
9
0.00 Hz
A146
ADD direction select
Two options:
00
…
Plus (adds
A145
value to the
output frequency setting)
01
…
Minus (subtracts
A145
value
from the output frequency
setting)
U
00
−
a150
Curvature of EL-S-curve at the
start of acceleration
Range is 0 to 50%
U
10. %
a151
Curvature of EL-S-curve at the
end of acceleration
Range is 0 to 50%
U
10. %
a152
Curvature of EL-S-curve at the
start of deceleration
Range is 0 to 50%
U
10. %
a153
Curvature of EL-S-curve at the
end of deceleration
Range is 0 to 50%
U
10. %
a154
Deceleration hold frequency
Sets the frequency to hold
deceleration, range is 0.0
to 400.0Hz
U
0.0 Hz
a155
Deceleration hold time
Sets the duration of deceleration
hold, range is 0.0
to 60.0 seconds
U
0.0 sec.