1-57
TROUBLESHOOTING
(2) Contents of Check Mode 2
The latest data of the first three indoor units only connected serially are indicated when more than three
indoor units are connected to one remote control switch.
By pressing the part of “TEMP” switch, the next display is indicated, If the part of “TEMP” switch is
pressed, the previous display is indicated.
>
>
Temperature Indication
Indication of Category Code
Indication of Temperature, etc.
1
Indoor Unit Intake
Air Temp. at
Thermistor (
o
C)
Indoor Unit
Discharge Air Temp.
at Thermistor (
o
C)
2
Indoor Unit Heat
Exchanger Liquid
Pipe Temp. (Freeze
Protection) (
o
C)
3
Outdoor Air Temp.
(
o
C)
4
Indoor Heat
Exchanger Gas
Pipe Temp. (
o
C)
5
Evaporating Temp.
at Heating (
o
C)
6
Control Information
7
Discharge Gas
Temp. at the Top of
Comp. Chamber (
o
C)
8
to next page
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".
Correspond to check mode 1 "
".