3-14
MAIN PARTS
3.7
High Pressure Switch and Pressure Switch for Control
(1) High Pressure Switch (for Protection)
When the discharge pressure reaches 3.3Mpa, compressor is stopped to protect the refrigerant cycle
components.
(2) Pressure Switch for Control
When the discharge pressure reaches 2.75MPa during heating operation, gas by-pass control or fan
control are performed.
Electrical Box
Upper Cover
Liquid
Tank
High
Pressure
Switch
High Pressure Switch
Pressure
Switch
for Control
Pressure Switch for Control
Discharge Pipe
Brazing Part
Brazing Part
RAS-3HVRG and 4HVRG
Electrical Box
Upper Cover
Liquid
Tank
High Pressure Switch
Pressure Switch
for Control
Discharge Pipe
Brazing Part
Brazing Part
RAS-5HVRG