TROUBLESHOOTING
1-27
“RUN” light flickers and “ALARM” is indicated on the remote control switch.
The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the alarm code is indicated on the display of the outdoor unit PCB.
In the case that the discharge gas superheat less than 10 deg. at the top of the compressor is
maintained for one hour, the alarm code is indicated.
Alarm
Code
Decrease of Discharge Gas Superheat
Is the thermistor on
top of compressor
good?
Is superheat value
under 10 degrees
o
C?
Yes
Check the high-pressure
and compressor discharge
gas temperature and
calculate superheat value
by outdoor unit PCB.
Check the high-pressure
and compressor discharge
gas temperature and
calculate superheat value
by outdoor unit PCB.
Faulty Thermistor
See page 1-35 for the
thermistor resistance.
No
No
No
Is the thermistor
installed correctly
on the compressor?
Yes
Install it correctly.
No
No
Is it at cooling or
heating mode when the
alarm has occurred?
Does outdoor
fan motor operate
correctly?
Is gas leaking?
Yes
Yes
Yes
No
Superheat: under
10 degrees
o
C?
Cooling
Heating Operation
Cooling Operation
Heating
Plug the connector
properly.
Repair leaks of gas.
Correctly charge refrigerant.
Remove the cause of
short path of discharge
air to the air intake of
the outdoor unit.
No
Is the connection on
indoor unit PCB and
intermediate connector
for expansion valve
connected properly?
No
Yes
Is refrigerant
correctly charged?
Yes
Yes
Charge correct refrigerant
volume.
Replace outdoor fan motor.