90
Alarm
Code
29
Abnormality of Low Pressure Sensor
●
The alarm code is flashed on the 7-segment display of the outdoor unit.
●
The alarm code is displayed on the wired controller of the indoor unit.
★
This alarm code is displayed when output voltage of the low pressure sensor decreases to 0.1V or less, or
increases to 4.9V or more during operation.