EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(3) Input Outdoor Fan Motor Start/Stop (Control Function No.4)
This is an auxiliary function to protect the outdoor unit from snow. When the input terminals for Outdoor
Fan Motor Start/Stop on the outdoor unit PCB are short-circuited during the compressor stoppage.
If outdoor ambient temperature is 10 °C or less, all the outdoor fan motors start operating. If the
compressor restarts operating, the outdoor fan motors will be restored to normal operation. If the input
terminals of Outdoor Fan Motor Start/Stop are opened during the outdoor fan motor operation following
the short circuit of these terminals, the outdoor fan motor will stop.
This function is possible only during the compressor stoppage (during Switch-OFF or Thermo-OFF of
the Switch-ON). Therefore, this function will not be possible even if the input signal is sent during the
normal cooling or heating operation.
An example of basic wiring when the Outdoor Fan Motor Start/Stop (Input 2) is set to 2 and 3 pins of CN1
by an external signal is shown below.
Notes:
●
This is an auxiliary function to protect the unit from snow. In snowy regions, make sure to protect the unit with a
snow-prevention roof, fence (field-supplied), or snow protection hood (optional). Otherwise, abnormal vibrations because
of an imbalanced propeller fan will be caused.
●
This function can not operate the outdoor fan when outdoor ambient temperature is higher than 10 °C.
●
If the fan motor fails during this function, stop all the outdoor fans to suspend this function. Check the alarm code and deal
properly with the failure, before next time the compressor is operated.
●
When setting the snow sensor switch for Outdoor Fan Motor Start/Stop, make sure that the continuous operating time is
30 seconds or more. Also Outdoor Fan Motor Start/Stop intervals shall be at least 10 minutes. Otherwise, malfunction of
the outdoor fan motors will be caused by frequent starts and stops.
●
The operation pattern of the outdoor fan can be changed by Function Setting “Fo”.
* Switch-ON: Some indoor units are running or staying.
Switch-OFF: All indoor units are stopped.
Содержание Set Free mini-HNRQ1 Series
Страница 8: ...1 Installation ...
Страница 50: ...43 Troubleshooting ...
Страница 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Страница 123: ...121 Maintenance ...
Страница 153: ...External Input Output and Function Setting 151 ...
Страница 167: ...Field Work Instructions 165 ...
Страница 172: ...Service Parts List 170 ...
Страница 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Страница 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Страница 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Страница 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Страница 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Страница 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Страница 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Страница 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Страница 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Страница 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Страница 187: ...HS2019266A ...