73
Protection Control Code and Retry Control Code
Indication
(SEG1)
Protection Control
Remark
Pressure Ratio Protection Control
To control the compressor frequency for prevention of operation with high/low
pressure ratio.
High Pressure Increase Protection
Control
To control the compressor frequency for prevention of high pressure
increase.
Inverter Current Protection Control
To control the compressor frequency for prevention of inverter current
increase in the outdoor unit during operation.
Inverter Fin Temperature Increase
Protection Control
To control the compressor frequency for prevention of inverter fin temperature
increase. The inverter fin temperature is detected at the inverter PCB.
Discharge Temperature Increase Protection
Control
To control the compressor frequency for prevention of discharge gas
temperature increase during operation.
Low Pressure Decrease Protection
Control
To control the compressor frequency for prevention of low pressure decrease.
High Pressure Decrease Protection Control
To control the compressor frequency for prevention of high pressure
decrease, which would interrupt smooth refrigerant distribution to indoor units
with different height and oil supply to the compressor.
Demand Current Control
To control the compressor frequency for fixing the inverter primary current
around the set value (40~100% of rated current for cooling).
Low Pressure Increase Protection
Control
To control the compressor frequency for prevention of low pressure increase.
Inverter Trip Retry
To stop the unit operation temporarily for protection of the compressor and
inverter. The operation will be restarted or stopped depending on the retry
frequency.
In
sufficient Voltage/Open Phase
Detection Retry
2. Troubleshooting Procedures
2.1 Alarm Code Indication of Wired Controller
Protection control code is displayed on the wired controller when a protection control is activated.
Refrigerant System No. 00
(Scope: 00~63)
Indoor Unit No.
01
(Scope: 00~63)
Alarm Code No.04
Press the Button Back
to Main Interface
Alarm Sign
Blinking
TROUBLESHOOTING
Содержание Set Free mini-HNRQ1 Series
Страница 8: ...1 Installation ...
Страница 50: ...43 Troubleshooting ...
Страница 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Страница 123: ...121 Maintenance ...
Страница 153: ...External Input Output and Function Setting 151 ...
Страница 167: ...Field Work Instructions 165 ...
Страница 172: ...Service Parts List 170 ...
Страница 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Страница 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Страница 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Страница 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Страница 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Страница 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Страница 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Страница 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Страница 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Страница 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Страница 187: ...HS2019266A ...