S1 series standard inverter
-101-
Function
code
Name
Detailed parameter description
Default
value
Modify
Sleep
Run
Set frequency curve:
Running frequency curve:
t1 < P01.20, the inverter does not run
t0=P01.34, sleep delay
Run
t2
t1
t0
Frequency lower
limit f0
Frequency f
Time t
Coast to
stop
t1+t2
≥
P01.20, the inverter runs
Setting range: 0.0
–3600.0s (valid when P.01.19 is
2)
P01.21
Restart after
power down
This function code sets the automatic running of
the inverter at next power-on after power down.
0: Disabled restart
1: Enable restart, namely the inverter will run
automatically after the time set by P01.22 elapses
if the starting conditions are met.
0
○
P01.22
Waiting time of
restart after
power down
This function code sets the waiting time before
automatically running at next power-on after
power down.
Output frequency
Running
Power off
Power on
Running
t
t1
t2
t1=P01.22
t2=P01.23
Setting range: 0.0
–3600.0s (valid when P01.21 is
1)
1.0s
○
P01.23
Start delay
This function code sets the delay of the inverter
’s
wake-up-from-sleep after running command is
given, the inverter will start to run and output after
the time set by P01.23 elapses to realize brake
release.
Setting range: 0.0
–600.0s
0.0s
○
P01.24 Stop speed delay 0.0
–600.0s
0.0s
○
P01.25
Open-loop 0Hz
output selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
○