S1 series standard inverter
-117-
Function
code
Name
Detailed parameter description
Default
value
Modify
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDI/HDIA virtual terminal
BIT5: HDIB virtual terminal
P05.11
2/3 Wire control
mode
This function code is used to set the 2/3 Wire
control mode.
0: 2-Wire control 1; integrate enabling function
with direction. This mode is the most popular
dual-line mode. Direction of motor rotation is
determined by the defined FWD/REV terminal
command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Hold
Forward
running
Reverse
running
1: 2-wire control 2; separate enabling function
with direction. In this mode, the defined FWD is
enabling terminal, and the direction is determined
by the state of REV.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stop
Stop
Forward
running
Reverse
running
2: 3-wire control 1; This mode defines Sin as
enabling terminal, and the running command is
generated by FWD, the direction is controlled by
REV. During running, the Sin terminal should be
closed, and terminal FWD generates a rising edge
signal, then the inverter starts to run in the
direction set by the state of terminal REV; the
inverter should be stopped by disconnecting
0
◎