5.2 SYSTEM WIRING DIAGRAM
Connect the units according to the following electric diagram:
TB
:
Terminal board
:
Field wiring
CB
:
Circuit breaker
:
Field-supplied
ELB
:
Earth leakage breaker
1,2
:
Outdoor-Indoor communication
:
Internal wiring
Operating Line
(Twisted shielded pair cable or shielded pair cable)
DC5V (Non-Pole Transmission, H-LINK system)
Outdoor unit
RAS-WHVNP(E)
YUTAKI S
YUTAKI S
Outdoor unit
RAS-WHNPE
Operating Line
(Twisted
shielded pair
cable or shielded
pair cable)
DC5V (Non-Pole
Transmission,
H-LINK system)
5.3 WIRING SIZE AND MINIMUM REQUIREMENTS OF THE PROTECTION DEVICES
!
C A U T I O N
•
Check to ensure that the field supplied electrical components (mains power switches, circuit breakers, wires, connectors and wire terminals) have
been properly selected according to the electrical data indicated on this chapter and they comply with national and local codes. If it is necessary,
contact with your local authority in regards to standards, rules, regulations, etc.
• Use a dedicated power circuit for the indoor unit. Do not use a power circuit shared with the outdoor unit or any other appliance.
Use wires which are not lighter than the polychloroprene sheathed flexible cord (code designation 60245 IEC 57).
Model
Power
supply
Operation mode
Max
current
(A)
Power supply
cables
Transmitting
cables
CB
(A)
ELB
(nº of poles/A/
mA)
EN60335-1
EN60335-1
RWM-(2.0-3.0)NE
1~ 230V
50Hz
Without electric heaters
0.2
2 x 0.75 mm² + GND
2 x 0.75 mm
2
5
2/40/30
With electric heater
15
2 x 2.5 mm² + GND
16
With DHW tank heater
15
2 x 2.5 mm² + GND
16
With electric and DHW tank heaters
29
2 x 6.0 mm² + GND
32
RWM-(4.0-6.0)NE
1~ 230V
50Hz
Without electric heaters
0.3
2 x 0.75 mm² + GND
5
2/40/30
With electric heater
29
2 x 6.0 mm² + GND
32
With DHW tank heater
15
2 x 2.5 mm² + GND
16
With electric and DHW tank heaters
43
2 x 10.0 mm² + GND
50
2/63/30
3N~ 400V
50Hz
Without electric heaters
0.3
4 x 0.75mm² + GND
5
4/40/30
With electric heater
10
4 x 2.5 mm² + GND
15
With DHW tank heater
15
4 x 2.5 mm² + GND
15
With electric and DHW tank heaters
24
4 x 6.0 mm² + GND
25
RWM-(8.0/10.0)NE 3N~ 400V
50Hz
Without electric heaters
0.6
4 x 0.75 mm² + GND
5
4/40/30
With electric heater
15
4 x 4.0 mm² + GND
20
With DHW tank heater
15
4 x 2.5 mm² + GND
15
With electric and DHW tank heaters
29
4 x 6.0 mm² + GND
30
?
N O T E
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL AND CONTROL SETTINGS