21
Compressor
Noisy Operation
Low Suction Pressure
Worn Compressor Parts
Knocking Runner
Worn Bearing
Loose Fan Belt
Partially Clogged
Refrigerant Short Charge
Loose Fixed Screw
Weak Foundation Installation
Liquid Line
Whistling
Inadequate Duct Work
Evaporator Fan
Noisy
Unremoved Shipping Washers
Overcharged Refrigerant
Shipping Washers
Noisy
Strainer
Liquid Refrigerant
Backing Up
TROUBLESHOOTING
High Suction Pressure
----------------------------- Reduce the Fresh Air Intake
----------------------------- Reinforce the Duct Insulation
----------------------------- Replace or Repair the Compressor
----------------------------- Charge Correct Refrigerant Quantity
----------------------------- See ”High Discharge Pressure”
Low Suction Pressure
----------------------------- Clean the Air Filter
----------------------------- Adjust the Belt Tension
----------------------------- Remove the Restriction
----------------------------- Adjust the Fan Speed
----------------------------- Repair or Replace the Motor
----------------------------- Remove Obstacles to Air Circulation
----------------------------- Repair or Replace if Required
----------------------------- Remove the Restriction
----------------------------- Add Refrigerant
----------------------------- See ”Low Discharge Pressure”
Noisy Operation
------- Remove the Washers
------- Charge the Correct Refrigerant Quantity
------- See ”Low Suction Pressure”
------- Replace or Repair the Compressor
------- Fix the Runner or Casing Properly
------- Replace the Bearing
------- Adjust Fan Belt Tension
------- Clean the Strainer
------- Add Refrigerant
------- Tighten All Fixed Screws
------- See the Installation Guide
------- Clean the Flexible Ducts
Evaporator
Air Flow
Low Suction Pressure
Restricted
Clogged Air Filter
Slipping Fan Belt
Restricted Duct
Low Fan Speed
Faulty Fan Motor
Short Cycling
Faulty Thermostat
Restricted Liquid Line and Suction Line
Low Refrigerant Charge
Evaporator Air
Inlet Temperature
Low
Low Discharge Pressure
Evaporator Air
Inlet Temperature
High Suction Pressure
High
Excessive Fresh Air Intake
Insufficient Duct Insulation
Defective Compressor Valve
Overcharged Refrigerant
High Discharge Pressure